Instruction Manual

Automation Components, Inc.
2305 Pleasant View Road | Middleton, WI 53562
Phone: 1-888-967-5224 | Website: workaci.com
Page 4
Version: 6.0
I0000822
FIGURE 9: MULTIPLE TRANSMITTER CONNECTIONS
P
ower Supply
+ -
+ -
+ -
Temp.Transmitter #1
Temp.Transmitter #N
Temp.Transmitter #2
-VDC+
Controller
Gnd AI1 AI2 AI3
= Connections
AI
1 = Controller Input #1
AI
2 = Controller Input #2
AI
3 = Controller Input #3
SOLUTION(S)
No power to board - check voltage at power terminal - should be
between +8.5 and 32 VDC.
RTD wires shorted. Disconnect sensor wires from terminal block and
check with ohmmeter. Reading should be close to either 100 or
1000 .
RTD Improper range of transmitter (too low). Check current or
voltage (model dependent) - should be between 4-20 mA, 1-5 V, or
2-10 V.
RTD opened. Disconnect sensor wires from terminal block and check
with ohmmeter. Reading should be close to either 100 or 1000 .
Improper range of transmitter (too high). Check current or voltage
(model dependent) - should be between 4-20 mA, 1-5 V, or 2-10 V.
Sensor check: Disconnect sensor wires from terminal block and
check with ohmmeter. Compare the resistance reading to the
Temperature vs Resistance curves located on ACI’s website.
Transmitter check: Make sure sensor wires are connected to
terminal block. Determine that the proper output is being
transmitted based on predetermined span:
1. Go to ACI Website, Span to Output Page:
http://www.workaci.com/content/span-output
2. Enter the low end of the span
3. Enter the high end of the span
4. Click on the output of the transmitter. This will generate a span
to output chart.
5. Measure output of transmitter.
6. Compare measured output to calculated output
Input power must be clean. Use twisted wires or shielded cable. RF
resistant power supply. Use a shielded cable to connect the sensor -
connect the shield to ground. Encase the board in a RF shielded enclosure.
TROUBLESHOOTING
PROBLEM
No Reading
Reading too Low
Reading too High
Reading is Inaccurate
RF Interference