326 Name MLXEV_ENCLHEAT_BAD
Description Temperature is over safe limit. Failure imminent.
Cause Room temperature is too high.
Fan failure.
Sensor failure.
Action Turn off the system and let it to cool down.
Adjust the room temperature.
Address ctl: 0 enclosure: 13 unit: 14
Severity 1 (Serious)
Source ExPro InPro
327
Name MLXEV_ENCLHEAT_CRITICAL
Description Temperature is above working limit.
Cause Room temperature is too high.
Fan failure.
Action Adjust the room temperature.
Replace fan.
Turn off the system.
Address ctl: 0 enclosure: 13 unit: 14
Severity 2 (Error)
Source ExPro InPro
328 Name MLXEV_ENCLHEAT_OK
Description Normal temperature has been restored.
Cause Faulty fan has been replaced.
Room temperature was reduced.
Action None
Address ctl: 0 enclosure: 13 unit: 14
Severity 4 (Information)
Source ExPro InPro
329 Name MLXEV_ENCLHEAT_NOTPRESENT
Description Temperature sensor is not present.
Cause Enclosure management connection is broken.
Management hardware failure.
Sensor is not present.
Action Refer to enclosure manufacturers service manual.
Address ctl: 0 enclosure: 13 unit: 14
Severity 4 (Information)
Source ExPro InPro
330 Name MLXEV_ENCLACCESS_CRITICAL
Description Enclosure access critical.
Cause Enclosure management connection is broken.
Management hardware failure.
Action Refer to enclosure manufacturers service manual.
Address ctl: 0 enclosure: 13
Severity 2 (Error)
Source ExPro InPro
331 Name MLXEV_ENCLACCESS_OK
Description Enclosure access has been restored.
Cause Enclosure has been fixed or replaced.
Action None
Address ctl: 0 enclosure: 13
Severity 4 (Information)
Source ExPro InPro