288 Name MLXEV_FMTHEAT_BAD
Description Over temperature. Temperature is above 70 °C.
Cause Room temperature is too high.
Fan failure.
Sensor failure.
Action Turn off the system and let it to cool down.
Adjust the room temperature.
Address ctl: 0 chn: 13 tgt: 14 Heat Sensor: 15
Severity 1 (Serious)
Source InP_old
289 Name MLXEV_FMTHEAT_CRITICAL
Description Temperature is above 50 °C.
Cause Room temperature is high.
Fan failure.
Action Replace fan.
Turn off the system.
Adjust the room temperature.
Address ctl: 0 enclosure: 13 unit: 14
Severity 3 (Warning)
Source ExP_old InP_old
290 Name MLXEV_FMTHEAT_OK
Description Normal temperature has been restored.
Cause Faulty fan has been replaced.
Room temperature was reduced.
Action None
Address ctl: 0 enclosure: 13 unit: 14
Severity 4 (Information)
Source ExPro InP_old
291 Name MLXEV_AEMI_OVER_TEMPERATURE
Description Over temperature.
Cause Room temperature is too high.
Fan failure.
Action Turn off the system and let it to cool down.
Adjust the room temperature.
Address ctl: 0 chn: 13 tgt: 14 Heat Sensor: 15
Severity 1 (Serious)
Source InP_old
292 Name MLXEV_FMTHEAT_NOTPRESENT
Description Storage cabinet temperature sensor is not present.
Cause Enclosure management connection is broken.
Management hardware failure.
Sensor is not present.
Action Refer to enclosure manufacturer’s service manual.
Address ctl: 0 enclosure: 13
Severity 4 (Information)
Source ExP_old InP_old
304 Name MLXEV_FMTSTWK_FAILED
Description Storage Works enclosure reported failure state.
Cause Power supply failed.
Fan failure.
Cabinet is too hot.
Action Refer to enclosure manufacturer’s service manual.
Address ctl: 0 chn: 13
Severity 1 (Serious)
Source InPro