Installation manual
Kitchen Hoods • Type I and Type II24
Maximum Increase in Static Pressure for Exhaust Air Balancing Baffle
(Fully Closed)
0
0.5
1
1.5
2
2.5
3
3.5
4
4.5
500 1000 1500 2000 2500 3000 3500
Duct Velocity FPM
Increase in Collar Staitc Pressure
This is a guide to assist in determining if multiple 
hoods on one fan can be balanced to have equal static 
pressure. For multiple hoods on one fan to achieve their 
designed exhaust flow, all of the hoods must have equal 
static pressure at their designed exhaust flow.
The laws of physics force the static pressure for each 
branch of a duct system on one fan to always be equal. 
This will happen by the flow rate increasing in low static 
branches and decreasing in high static branches until 
the static pressure is equal in all branches.
Checking for Balance
Every hood with exhaust air balancing baffles (EABB) 
has a range for its static pressure. The low static 
pressure number (when EABB is open) in this range is 
given by the standard calculation for hood static and is 
printed on the CAPS submittal page for that hood. The 
high static pressure number (when EABB is closed) in 
this range can be found by calculating the maximum 
potential increase of static and adding that value to the 
low static pressure number.
High static pressure number = low static pressure 
number + maximum increase
The maximum potential increase in static is given in the 
graph, or can be calculated from the following formula:
Maximum Increase = 0.00000036 x (Duct velocity)
2
Refer to the examples.
Example 1:
Hood 1:  Ps = 0.58 in. wg 
  Duct Velocity = 1900 ft/min.
Hood 2:  Ps = 0.44 in. wg 
  Duct Velocity = 1800 ft/min.
Hood 2 has the lower Ps, at 1800 ft/min. the maximum 
increase in Ps is 1.17. The range for Hood 2 is 0.44 to 
1.61. Hood 1 is less than 1.61 so these hoods can be 
balanced.
Example 2:
Hood 3:  Ps = 2.00 in. wg 
  Duct Velocity = 2000 ft/min.
Hood 4:  Ps = 0.44 in. wg 
  Duct Velocity = 1500 ft/min.
Hood 4 has the lower Ps, at 1500 ft/min. the maximum 
increase in Ps is .81. The range for Hood 4 is 0.44 to 
1.25. Hood 3 is higher than 1.25, so these hoods cannot 
be balanced.
NOTE
For many systems, exhaust air balancing baffles may 
not be needed on the hood that has the highest static 
pressure. The exception to this is if the individual 
ductwork has uneven static pressures.
NOTE
When sizing the fan, use the static pressure from the 
highest hood and sum the CFM from all the hoods.
Step 1: Find the hood with the lowest static pressure 
as shown on the CAPS submittal pages.
Step 2: Calculate the high static pressure number for 
this hood as instructed above.
Step 3: Compare this high static pressure number to 
the low static pressure number of the remaining hoods. 
If the remaining hood’s low static pressure number is 
lower than the high static pressure number calculated, 
then the system can be balanced; if the low static 
pressure number is higher than the calculated high 
static pressure number, then the system cannot be 
balanced. 
Exhaust Air Balancing Baffles










