Kitchen Hoods • Type I and Type II 15
CAUTION
According to NFPA 96, Ch. 8-3 Replacement Air: 
Replacement air quantity shall be adequate to prevent 
negative pressures in the commercial cooking area(s) 
from exceeding 4.98 Pa (0.02 in. wg).
NOTE
The airflow rates were established under controlled 
laboratory conditions.
NOTE
Greater exhaust and/or lesser supply air may be 
required for complete vapor and smoke control in 
specific installations.
To determine the proper dining room air 
balance:
1. Refer to engineering drawings to determine total 
exhaust CFM from dining areas. (exhaust fans, 
heating and air conditioning units, rest rooms, etc.)
2. Determine the total CFM of make-up air supplied to 
dining area.
3. Subtract #1 from #2 above. If the result is a negative 
number, a negative pressure is present in the dining 
area. In this case, kitchen exhaust odors could be 
drawn from the kitchen to the dining area. Therefore, 
exhaust or supply air should be adjusted to provide a 
slight positive pressure in the dining area.
Balancing the Kitchen Exhaust System
To determine proper kitchen air balance:
1. Refer to engineering drawings to determine total 
exhaust from the kitchen area. (exhaust hoods, 
dishwasher hoods, etc.)
2. Determine total CFM of make-up air supplied to 
kitchen area. (make-up air hoods, heating and air 
conditioning units, etc.)
3. Subtract #1 from #2 above. The result should be a 
negative number. If the result is a positive number, 
a positive pressure is present in the kitchen area. 
Kitchen odors could be forced into the dining 
area. Also, a positively balanced kitchen area can 
adversely affect the performance of the exhaust 
hood.