Installation manual
9
Note: The installation of the hoods shall be in accordance with NFPA 96 (latest edition), Standard for 
Ventilation Control and Fire Protection of Commercial Cooking Operations.
Fig. 14 shows the locations where the 
hood must be fastened. If a Back Supply 
Plenum is part of the hood system, 
please see pages 8-9, Back Supply 
Plenum/Hood Installation. 
To hang the hood:
1)  Locate the studs in the wall.
2)  Drill 1/2 in. (13 mm) diameter holes in 
the hood mouting flange. Be sure to 
align to wall studs.
3)  Lift hood into a level position and 
lag bolt hood to wall (fasteners by 
others).
4)  Bolt 1/2 in. (13 mm) threaded rod into 
the hanger brackets.
5)  Fasten threaded rod to ceiling 
supports then level the hood. 
Hood Mounting Instructions
Hanging the Hood with Back Supply Plenum
Before hanging the hood according to the hood 
installation instructions, please check the following:
1.  Make sure the back supply unit is properly 
secured, as described in steps 5 and 6, page 8.
2.  Any filler panels should be attached to the hood 
before the hood installation.
To hang the hood:
1.  Lift the hood and position it so the top of the 
hood is even with the back supply (Fig. 13). This 
height should correspond to the UL hanging 
height of the hood.
2.  After the hood is hung from the ceiling, a hood 
mounting flange may be fastened to the back 
supply using sheet metal screws (by others). 
Pilot holes are recommended.
3.  Connect the remaining ductwork for the back 
supply and the hood. Caulk all mating seams 
and surfaces of the back supply, the hood, and 
the wall.
Hanger Brackets
Mounting Flange
Fig. 14
Fig. 13