BACnet Int egration Guide – DOAS_08.000 Rev 2 Page | 8
Alarm Table - Latest Alarm (IV-5)
13 Ret urn Air RH - Sensor Value Not Valid 106 Low Discharge Pr essure - First Invert er
14 Space RH - Sensor Value Not Valid 107 High Suction Pressure - First Inverter
15 Out side RH - Sensor Value Not Valid 108 Low Suction Pressure - First Inverter
16 Low Pressure Switch - Circuit A 109 High Curr ent - First Inverter
17 Low Pressure Switch - Circuit B 110 High Pressure Ratio - First Invert er
20 High Pressure Switch - Circuit A 111 Low Pressure Ratio - First Invert er
21 High Pressure Switch - Circuit B 112 Low Delt a P - First Inverter
24 Damper End Swit ch Fail - Dam pers are not open 113 High Discharge Press - First Invert er
25 Exhaust Fan 1 Run - Stat us Not Proven 114 Compr essor Staging - Order Skipped
26 Filters are Dirt y - Replace Filt ers 115 Heat Pump Heat ing - Locked Out
27 Cond Drain Pan Full - Check Drain 116 EVD 1 Error - Unexpect ed Position
28 Exp Boar d 1 St at us - Board is Offline 117 High SDT Lockout - Circuit A
29 Exp Boar d 2 St at us - Board is Offline 118 High SDT Lockout - Circuit B
31 Exp Boar d 4 St at us - Board is Offline 121 Invert er 1 Alarm -
32 Non-Volat ile M emory Er - Contact Tech Support 123 Invert er 1 Lockout - Cycle Pow er t o Unit
33 Space 1 CO2 - Sensor Value Not Valid 125 Inverter 1 Foldback - Out put Current
34 Space St at ic Pressure - Sensor Value Not Valid 126 Inverter 1 Foldback - Input Current
35 Supply Duct St at Press - Sensor Value Not Valid 127 Inverter 1 Foldback - Inverter Tem p
36 Ret urn Duct Stat Press - Sensor Value Not Valid 131 Invert er 1 Comms Lost - Compressor Offline
37 Supply Fan AFM S - Sensor Value Not Valid 133 Space Ther mostat 1 - Sensor Offline
38 Exhaust Fan AFM S - Sensor Value Not Valid 134 Space Ther mostat 2 - Sensor Offline
39 Out side Damper AFM S - Sensor Value Not Valid 135 Space Ther mostat 3 - Sensor Offline
40 Space Set pt Adj Slider - Sensor Value Not Valid 136 Space Ther mostat 4 - Sensor Offline
41 Space 2 CO2 - Sensor Value Not Valid 137 IG Furnace 1. No flame - aft er 3 tries
42 Ret urn CO2 - Sensor Value Not Valid 138 IG Furnace 1 Large - no flame aft er 3 tries
43 Discharge Pr ess Ckt A - Sensor Value Not Valid 139 IG Furnace 1 combust - fan high pressure sw itch
44 Discharge Pr ess Ckt B - Sensor Value Not Valid 140 IG Furnace 1 Ignit ion - cont roller alarm
47 Suction Press Ckt A - Sensor Value Not Valid 141 IG Furnace 1 pressure - swit ch fault alarm
48 Suction Press Ckt B - Sensor Value Not Valid 142 IG Furnace 1 combust - fan proving alarm
51 Discharge Temp Ckt A - Sensor Value Not Valid 143 IG Furnace 1 - M ax Retries
52 Discharge Temp Ckt B - Sensor Value Not Valid 144 IG Furnace 1 - High Limit Trip
55 Suction Temp Ckt A - Sensor Value Not Valid 145 IG Furnace - pCOe 1 Offline
56 Suction Temp Ckt B - Sensor Value Not Valid 146 IG Furnace 1 IC fault - Check Furnace Wir ing
59 Ckt A High Sat urated - Discharge Temperat ure 147 IG Furnace 2 No flame - aft er 3 tries
60 Ckt B High Saturat ed - Discharge Temperat ure 148 IG Furnace 2 Large - no flam e af ter 3 tries
63 Supply Air Temperat ure - Low Limit Shutdow n 149 IG Furnace 2 combust - fan high pressure switch
64 Heat Wheel Rotation - Not Detect ed 150 IG Furnace 2 Ignit ion - cont roller alarm
65 Slave Unit 1 Offline - 151 IG Furnace 2 pressure - swit ch fault alarm
66 Slave Unit 2 Offline - 152 IG Furnace 2 combust - fan proving alarm
67 Slave Unit 3 Offline - 153 IG Furnace 2 - M ax ret ries
68 Slave Unit 4 Offline - 154 IG Furnace 2 - High Limit Trip
69 M ast er Unit Offline - 155 IG Furnace - pCOe 2 Offline
70 Heat Pump Defrost - M ode is Act ive 156 IG Furnace 2 IC fault - Check Furnace Wiring
71 M ulti Devices per Ch - Cont act Tech Support 157 Out side Air GreenTrol - Offline or Flow Error
74 Shut down Cont act - In Alarm Position 158 Exhaust Air GreenTrol - Offline or Flow Error
75 Comp M aint enance Alarm - Run Hours Set pt Reached 159 Supply Air GreenTrol - Offline or Flow Error
76 Supply Air Temperat ure - High Limit Shutdown 169 ER Wheel High - Different ial Pressure
77 Space High St atic Pres - Shut dow n 170 OA Damper Fault - Not Econ and should be
78 Int ernal Board Temp - Exceeds -40F or 158F 171 OA Damper Fault - Econ and shouldn't be
79 BM S Offline - Wat chdog is FALSE 172 OAD Fault - Damper not M odulat ing
80 Cooling Coil Set pt Input - Value is not valid 173 OAD Fault - Excess Out door Air
81 Sup Air Set pt Input - Value is not valid 174 IG Furnace 1 - Combustion Fan Alarm
82 BACnet License - Not Installed 175 IG Furnace 2 - Combust ion Fan Alarm
83 Low Suction SH ExV A - EVD 1 Alarm 176 Supply Fan - VFD Offline
84 Low Suction SH ExV B - EVD 1 Alarm 177 Exhaust Fan - VFD Offline
85 LOP A EVD 1 - Low Operat ing Pressure 178 Ret urn Fan - VFD Offline
87 MOP A EVD 1 - M ax Operating Pressure 179 Energy Recovery - VFD Offline
89 EEV A EVD 1 - M ot or Alarm 180 Embedded EVD Error
91 Low Suction A EVD 1 - Refrigerant Temp 181 SF VFD Alarm - Check VFD
93 High Condensing Temp - EVD 1