BACnet Int egrat ion Guide – DOAS_08.000 Rev 2 Page | 7
This may be desired if t he BM S is running a reset routine on the setpoint s and would
like to revert to a default state if communication is lost. It is recommended to be used
with ret urn to default enabled, and a known relinquish default is saved.
When this box is checked by a user, the controller will write the present value of
variables to the relinquish default for all binary and analog value BACnet objects that
are comm andable. The function operat es in the background and takes approximately
30 seconds to complete.
This is desired to save any Test and Balance settings adjusted locally on the controller
to be the BACnet relinquish default values. Alternatively, these values could be read
and written to the relinquish default variables by the BM S system.
BINARY TEXT
If for any reason, the state text is missing from binary objects, checking this
box will cause the controller to re-write the act ive and inactive text values.
DOAS Reference Tables
STATUS M ODE TABLE
The following analog values can appear in the point to tell the building aut omation the current mode of operation of the
unit. Values may rotate every three seconds.
Status M ode Table (AV-40)
Analog
Value
M ode
Analog
Value
M ode
Analog
Value
M ode
0 Off/ St andby 12 System Disabled 23 Dehumidifying
1 Unoccupied Start 13 Remot e Off 25 Hot Gas Reheat Purging
2 Occupied St art 14 Syst em Shut down Alarm 26 Energy Recovery Defrost Active
3 Opening Dampers 15 Pressurization Only 29 Dehumidifying wit h Heat
5 Dampers Open 16 Exhaust Only 30 M anual Overrides Active
6 Fan St art Delay 17 Fan Only Purge 31 Expansion Board Offline
7 Exhaust Fan St art 18 Case Heat Active 33 Energy Recovery Active
8 Supply Fan Start 19 Fans Only 34 Hot Gas Reheat Active
9 Heat/ Cool St artup Delay 20 Economizing 35 M orning Occupancy Sequence
10 Syst em On 21 Cooling 36 Heat Pump Defrost Active
11 Soft Shut dow n 22 Heating
ALARM TABLE
This table displays the latest alarm that is active in the unit controller.
Alarm Table - Latest Alarm (IV-5)
0 No Active Alarms 94 Sens S1 EVD 1 - Sensor Value Not Valid
1 Supply Fan 1 Run - Status Not Proven 95 Sens S2 EVD 1 - Sensor Value Not Valid
2 Freeze Prot ection - Thermostat Tripped 96 Sens S3 EVD 1 - Sensor Value Not Valid
3 High Supply Duct - St atic Pr essure 97 Sens S4 EVD 1 - Sensor Value Not Valid
4 Low Return Duct - Static Pressur e 98 EVD 1 EEPROM Damaged - Call Tech Support
5 Out side Air Temp - Sensor Value Not Valid 99 Incomplet e Closing - EVD 1
6 Supply Air Temperature - Sensor Value Not Valid 100 Emergency Closing - EVD 1
7 Cold Coil 1 Tem p - Sensor Value Not Valid 101 EVD 1 Batt ery -
9 Exhaust Air Temp - Sensor Value Not Valid 102 FW Incompat ibility - EVD 1
10 M ixed Air Temperat ure - Sensor Value Not Valid 103 EVD 1 Config Error -
11 Ret urn Air Temperature - Sensor Value Not Valid 104 EVD 1 Comm - EVD 1 is Offline
12 Space Temperature - Sensor Value Not Valid 105 High Discharge Temp - First Invert er