User Guide

DOAS BACnet Quick Start Guide January 2023
BACnet Quick Start Guide
1 W ire Network Connection A Ethernet Port Lights
2 Adjust BACnet Network Settings
M enu Structure Reference
M ain M enu
Ct rl Variables
Advanced
Login
Network Settings
2.1 – Enter User Password 2.2 – BACnet M S/ TP Settings
2.2 BACnet IP Settings
3 Command Unit Operation
1. Enable Unit
2. Control Occupancy
3. Reset Alarms
4. Global Alarm Not ification
5. Control Temperature Set point
(optional)
Object Object Nam e Object Description
Active Text Inact ive Text
Variable Type
BV-2 Syst em_Enable M aster system enable/ disable point . Enabled Disabled
BV-3 BM S_Occupancy_Com mand Occupancy Command Unoccupied Occupied
BV-4 Reset_All_Alarms Alarm Reset Command Reset Normal
BV-23 Global_Alarm Alarm Notification (any alarm by default) Alarm Normal
AV-1 Tem perature_Setpoint
Set s the active t emperat ure set-point based on mode of
operat ion (space set point , ret ur n setpoint or supply
setpoint). Not applicable for outside reset .
Default = 72°F
M in = 50°F; M ax = 100°F
Ethernet Port Lights
Green: Connected
Yellow : On = 100M bps
Off = 10 M bps
A
A
c.pCO St andard Controller
c.pCO Mini Cont roller
M S/ TP
TCP/ IP