Data Logger User Manual
AccuCold, Div of Felix Storch, Inc. | R005-07102018                                                                           
4 
Buttons Description   
Default Data Logger Settings 
Code 
Function 
Range   
Default Setting   
*Please enter the correct temperature units 
o
F /
 o
C 
C1 
High temp. alarm 
C2    ~    100
o
C /212
 o
F   
8.0 
o
C   
C2 
Low temp. alarm 
-45
o
C /-49
 o
F ~ C1 
2.0 
o
C 
C3 
Alarm hysteresis 
0.1~20.0
o
C   
0.2~36
 o
F   
1.0
 o
C /2.0
 o
F   
C4 
Alarm delay 
00~90 min 
0 min 
C5 
Start delay 
00~90 min 
0 min 
CF 
Temperature Unit 
o
C =Celsius     
o
F =Fahrenheit 
o
C 
E5 
Offset temperature 
-20~20
o
C   
-36~36
 o
F   
0.0
 o
C/
 o
F 
L1 
Logging interval 
00~240 min 
05 min 
PAS 
Password 
00 ~99   
50 
Programming the Data Logger   
Password Input   
From the main display screen:   
Hold  the  SET  key  for  3  seconds.  Use  the  up  and  down  arrows  to  adjust  the 
password to the correct password. By default the correct password is 50.     
Press SET key ONCE to confirm the settings. 
High Alarm 
Temperature Setting   
By default, the high and low alarm settings are 8 
o
C and 2 
o
C respectively. To reset high 
alarm and low alarm temperature settings, follow instructions below.     
From the main display screen:   
Hold the SET key for 3 seconds. Enter the correct password then press the SET key 
ONCE to  enter  the  HI  Temp  Alarm  setting  mode.  Use  the  up  and  down  arrows  to 
adjust the temperature accordingly.    Press SET key ONCE to confirm the settings. 
REC/STOP 
Press REC/STOP to STOP or RECORD data.     
MAX/MIN 
Press for 3 seconds to ERASE the MIN and MAX temperature 
history.   
DL 
Copy the recorded data (CSV file) to USB   
SET 
Hold the SET button to cycle through configuration settings. 
Up/Down keys to change settings. Press and hold either key to 
advance the values rapidly.   