Instruction Manual
15 
If setting C8 is set to “0”, then after alarm is canceled, the alarm relay does not close. If C9 is set to 
“0”, then after the alarm cancel button is pushed, the buzzer does not restart. 
If setting other numbers, then after reaching delay time, buzzer sounds one more time. (Under the 
condition of alarm not terminating) 
Abnormal work mode: When air sensor is short-circuited or high temperature over limit (>
66°C/151°F), "1H" is displayed; when air sensor is open-circuited or low temperature over limit (<-
40°C/°F) "1L" is displayed. Compressor will enter the force running mode, according to C10, C11 set 
parameters running in sequence. 
When product sensor is short-circuited, open-circuited or over limit (>66°C/151°F), alternate display 
2H and air temperature, the product temperature sensor open-circuited or low temperature over limit 
(<-40°C/°F), alternate display 2L and air temperature. 
Instrument running alarm indication list 
Alarm type 
Compressor running 
Display flash 
Refrigerator high temp. alarm 
Compressor on 
H1 delay alarm 
Refrigerator low temp. alarm 
Compressor off 
L0 delay alarm 
Air temp. sensor short-circuited 
Press C10, C11 to run the 
comp. 
1H in time alarm 
Air temp. sensor open-circuited 
Press C10, C11 to run the 
comp. 
1L in time alarm 
Product temp. sensor short-
circuited 
2H in time alarm 
Product temp. sensor open-
circuited 
2L in time alarm 
Product temperature high temp. 
Limit alarm 
H2 delay alarm 
Product temperature low temp. 
Limit alarm 
L2 delay alarm 
Electric supply off alarm 
EEL flash and alarm in 
time 
Door open delay alarm 
Dr flash and delay alarm 
When the door is open, the light switch can turn the light on and off. 