User manual

Manual WWP-IIRO-8
5
Chapter 1: Introduction
Features
Wireless Digital Input / Relay Output Module Pair
Each input on one unit is mapped to control the corresponding relay automatically in the other
7-mile line of site communications over integrated non-licensed FCC radio modems
Removable omni-directional antenna without requiring access to inside of enclosure
900 MHz unlicensed radio modem with frequency hopping spread spectrum technology
NEMA4 enclosure for harsh atmospheric or marine environments
Two water-tight cable glands for power and I/O field wiring
Inputs accept from 3 to 33V (DC or AC rms) as an “on” signal
Relays can switch up to 60 VDC and up to 125 VAC
Switching current capability up to 0.5 A at 125 VAC; 1 A at 24 VDC
Auto-detection seeks for communications from each other when power applied
Each unit in the pair has the following
8 optically-isolated, non-polarized digital inputs
Jumper-selectable filters per input for electrically noisy environments
8 SPDT electromechanical relay outputs
Internal removable screw terminal boards for simplified wiring
Applications
Factory Automation
Energy Management and Conservation
Agricultural and Irrigation Systems
Security
Refinery
Marinas and Ports
Lighting
Traffic and Mobile
Functional Description
This product features a pair of intelligent 8-bit parallel digital I/O units that communicate with each
other without requiring a connection to a PC. When an input is turned on at one of the units, it will
cause the corresponding relay to switch on the other unit. As long as the input stays active, the
corresponding relay will remain energized on the other unit. If power is lost to either unit, the other
unit will retain the last valid commanded position for the relays. When power is restored to the
first unit, any changes that occurred to the eight inputs would then be communicated to the unit
that didn’t lose power, and the relays would follow the newly reported state.