System information

87
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Maintenance SRD
Maintenance Others
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: MAIN_SRD
PIC 5 PATH: Main Menu Maintenance Menu Maintenance SRD
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Diffuser Target Pos diff_tgt % RO
2 Diffuser Fault diffault NO/YES RO
3 SRD Rotating Stall Alarm diff_alm NO/YES RO
4 Calculated SRD Position srd_a % RO
5 Calc High Lift SRD Pos srd_1 % RO
6 Calc Low Lift SRD Pos srd_2 % RO
7 Calc Actual Lift lift_a °F RO
8 VDO High Lift Load Line lift_1 °F RO
9 VDO Low Lift Load Line lift_2 °F RO
10 VDO Logic Start Delay strt_tmr min RO
11 SRD Stall Closure Time stalltmr min RO
CCN TABLE NAME: MAIOTHER
PIC 5 PATH: Main Menu Maintenance Menu Maintenance Others
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 5V Sensor Power Monitor tran_v V RO
2 Evap Pres Trans Volts evapp_v V RO
3 Cond Pres Trans Volts condp_v V RO
4 Econ Pres Trans Volts econp_v V RO
5 Diffuser Pres Tran Volts diffp_v V RO
6 Oil Sump Pres Tran Volts opsmp_v V RO
7 Oil Sup Pres Trans Volts opdis_v V RO
8 Evap Enter Water Volts evewp_v V RO
9 Evap Leave Water Volts evlwp_v V RO
10 Cond Enter Water Volts cdewp_v V RO
11 Cond Leave Water Volts cdlwp_v V RO
12 Prestart Check Status pre_chck NO/YES RO
13 GV1 Pos at Startup OK gvpos_ok NO/YES RO
14 OIL PD at Startup OK oilpd_ok NO/YES RO
15 HGBP Pos at Startup OK hgbp_ok NO/YES RO
16 Damper at Startup OK dmp_ok NO/YES RO
17 Oil Pump Req Oil Heater op_heat NO/YES RO
18 Oil Pump Req Prestart op_prest NO/YES RO
19 Oil Pump Req Startup op_start NO/YES RO
20 Oil Pump Req Shutdown op_shut NO/YES RO
21 Oil Pump Req Swift Rst op_srst NO/YES RO
22 Evap Pump Req Startup ep_start NO/YES RO
23 Evap Pump Req Diagnostic ep_diag NO/YES RO
24 Evap Pump Req Freeze ep_freze NO/YES RO
25 Evap Pump Req Shutdown ep_shut NO/YES RO
26 Evap Pump Req Pumpdown ep_pdown NO/YES RO
27 Cond Pump Req Prestart cp_prest NO/YES RO
28 Cond Pump Req Startup cp_start NO/YES RO
29 Cond Pump Req Override cp_overr NO/YES RO
30 Cond Pump Req Shutdown cp_shut NO/YES RO
31 Cond Pump Req Tower cp_tower NO/YES RO
32 Cond Pump Req Diagnostic co_diag NO/YES RO
33 Cond Pump Req Freeze cp_freze NO/YES RO
34 Cond Pump Req Pumpdown cp_pdown NO/YES RO
RO Read Only
RW Read/Write