System information

84
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Swift Restart
Master Slave
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: MAISWRST
PIC 5 PATH: Main Menu Maintenance Menu Swift Restart
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 SRD Position @Shutdown srd_shut 0 to 100 % RO
2 VFD Speed @Shutdown vfd_shut 0 to 100 % RO
3 GV1 Position @Shutdown gv1_shut 0 to 100 % RO
4 Evap Sat Temp @Shutdown est_shut –40 to 280 °F RO
5 Power Recovery Duration pd_dur 0 to 1 min RO
6 Power Down Active power_dn NO/YES RO
7 Auto Restart Active auto_rst NO/YES RO
8 Swift Restart Active sw_rst NO/YES RO
CCN TABLE NAME: MAIN_MS
PIC 5 PATH: Main Menu Maintenance Menu Master Slave
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Unit is Lead or Lag
0 = Disable
1 = Lead
2 = Lag
lead_lag
0 to 2 RO
2 Master Control Type
0 = Local
1 = Network
2 = Remote
3 = Local Sched
ms_ctrl
0 to 3 RO
3 Slave Control Type
0 = Local
1 = Network
2 = Remote
3 = Local Sched
sl_ctrl
0 to 3 RO
4 Lead Lag Communication ll_comm TRUE/FALSE RO
5 Lead Lag Chiller Fault
0 = No
1 = Lead
2 = Lag
3 = Both
ll_fault
0 to 3 RO
6 Slave Run Status lagstat 0 to 14 RO
7 Slave Start/Stop lag_s_s START/STOP RO
8 Capacity Decrease CAP_DECL NO/YES RO
9 Capacity Inhibit CAP_INHL NO/YES RO
10 Master Chiller Running MST_RUN NO/YES RO
11 EWT Control Option DSABLE/ENABLE RO
12 Demand Limit Source 0 to 1 RO
13 Lag Start Timer lagstart 0 to 60 min RO
14 Lag Stop Timer lagstop 0 to 60 min RO
15 Prestart Fault Timer preflt 0 to 30 min RO
16 Pulldown Timer pulltime 0 to 30 min RO
17 Pulldown: Delta T / Min pull_dt 0 to 100 °F RO
18 Lead/Lag Hours Delta ll_hr_d –99999 to 99999 hours RO
19 Overrid Control Point ctrpntov 10 to 160.0 °F RO
20 Overrid Act Demand Limit demlimov 10 to 100.0 % RO
RO Read Only
RW Read/Write