System information

82
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Override Control
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: OVERRIDE
PIC 5 PATH: Main Menu Maintenance Menu  Override Control
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Cond Press Trip Value cp_trip psig RO
2 Cond Press Override Flag cpov_fl NO/YES RO
3 Low DSH Override Flag dshov_fl NO/YES RO
4 Required DSH dsh_req °F RO
5 High Lift Override Flag lftov_fl NO/YES RO
6 Low SST Override Flag sstov_fl NO/YES RO
7 High Motor Temp Over mtov_fl NO/YES RO
8 High Bearing Temp Over tbov_fl NO/YES RO
9 Evap Sat Override Temp ert_over °F RO
10 DSH Increase Step dshinstp % RO
11 DSH Decrease Step dshdestp % RO
12 Low Sour Temp Over Flag lstov_fl NO/YES RO
13 DGT Override Flag dgtov_fl NO/YES RO
14 High Motor Current Flag ampov_fl NO/YES RO
15 Capacity Inhibit Ramping cap_inhr NO/YES RO
16 Capacity Inhibit Demand cap_inhd NO/YES RO
17 Capacity Decrease Demand cap_decd NO/YES RO
18 Capacity Inh Override cap_inho NO/YES RO
19 Capacity Dec Override cap_deco NO/YES RO
20 Capacity Inh Surge cap_inhs NO/YES RO
21 Capacity Decrease Surge cap_decs NO/YES RO
22 Capacity Inh Low SST capinhst NO/YES RO
23 Capacity Dec Low SST capdecst NO/YES RO
24 Capacity Inh High Lift capinhlf NO/YES RO
25 Capacity Inh Cond Pres capinhcp NO/YES RO
26 Capacity Dec Cond Pres capdeccp NO/YES RO
27 Capacity Inh Motor Temp capinhmt NO/YES RO
28 Capacity Dec Motor Temp capdecmt NO/YES RO
29 Capacity Inh Hi Current capinham NO/YES RO
30 Capacity Dec Hi Current capdecam NO/YES RO
31 Capacity Dec Low Temp capdecls NO/YES RO
32 Capacity Inh DSH capinhsh NO/YES RO
RO Read Only
RW Read/Write