System information

81
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Capacity Control
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: CAPACTRL
PIC 5 PATH: Main Menu Maintenance Menu  Capacity Control
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Total Error + Resets tot_err °F RO
2 Control Point Error ctrl_err °F RO
3 Controlled Water Temp ctrl_wt °F RO
4 Control Point ctrl_pnt °F RO
5 Actual Set Point setpoint °F RO
6 Entering Water Change DT ewt_dt °F RO
7 Enter Water Temp Reset ewt_res °F RO
8 Leaving Water Temp Reset lwt_res °F RO
9 Discharge Gas Temp Reset dgt_res °F RO
10 Target GV1 Pos gv1_tgt % RO
11 GV1 Pos Change Delta gv1delta % RO
12 GV1 Change Flag gv1_chg 0 to 2 RO
13 0 = Stop, 1 = Change, 2 = Cont RO
14 VFD Speed Change Flag vfd_chg 0 to 2 RO
15 0 = Stop, 1 = Change, 2 = Cont RO
16 Target VFD Speed vfd_tgt % RO
17 VFD Speed Change Delta vfd_dlta RO
18 Capacity Inhibit Flag cap_inh NO/YES RO
19 Capacity Decrease Flag cap_dec NO/YES RO
20 Condenser Water Delta T cdw_dt °F RO
21 Chilled Water Delta T chw_dt °F RO
22 Pulldown Set Point pull_set % RO
23 Demand Limit Inh Clamp deinhclm % RO
24 Ramping Demand Limit Val ramp_dem NO/YES RO
25 Compressor is Running comp_run NO/YES RO
26 Comp1 Run State Val cm_stat1 0 to 14 % RO
RO Read Only
RW Read/Write