System information
8
IOB (Input/Output Board) — The IOB is supplied
from a 24 VAC supply reference to earth ground. The compo-
nents listed in Tables 2-5 are available at the user’s terminal
block on the IOB. Some are available only if the unit is operat-
ing in Remote mode. Figures 6-9 show IOB wiring diagrams.
Figures 10-13 shows additional control wiring.
LEN Communication Cables — The communica-
tion transmission cables have the following electrical charac-
teristics:
• 2 signal conductors and one ground conductor of 20
AWG or larger, 100% shielded
• One tinned copper braid (65% coverage)
Recommended cables are shown below:
Table 2 — IOB1 Connections at User’s Terminal Block
NOTES:
1. See Fig. 6 for IOB1 wiring diagram.
2. For pressure readings, only Vout (output) terminal is indicated.
See Fig. 6 for Vin (+) and ground (–).
3. Defaults are shown. In some cases the IOB can be configured
differently depending on job requirements.
Table 3 — IOB2 Connections at User’s Terminal Block
NOTES:
1. See Fig. 7 for IOB2 wiring diagram.
2. For pressure readings, only Vout (output) terminal is indicated.
See Fig. 7 for Vin (+) and ground (–).
3. Defaults are shown. In some cases the IOB can be configured
differently depending on job requirements.
USAGE CABLE
Intra-building Belden 8772
High temperature Belden 85240
Plenum Belden 89418
DESCRIPTION CHANNEL TERMINAL TYPE OPTIONAL
Entering Chilled Water Temperature AI1 J16-1,5 5 k —
Leaving Chilled Water Temperature AI2 J16-2,6 5 k —
Entering Condenser Water Temperature AI3 J16-3,7 5 k —
Leaving Condenser Water Temperature AI4 J16-4,8 5 k —
Evaporator Refrigerant Liquid Temperature AI5 J15-6,12 5 k —
Discharge Gas Temperature AI6 J15-5,11 5 k —
Condenser Pressure AI7 J15-4 5 VDC —
Evaporator Pressure AI8 J15-3 5 VDC —
Economizer Pressure AI9 J15-2 5 VDC —
Chiller Running (ON=20mA, OFF=4mA, TRIPOUT=8mA,
READY=12mA)
AO1 J14-1,4 4-20 mA Yes
Chiller Lockout Input DI1 J13-5 24 VAC Yes
Fire Alarm Interlock DI2 J13-6 24 VAC Yes
Remote Contact Input DI3 J13-7 24 VAC Yes
Remote Emergency Stop Input DI4 J13-8 24 VAC Yes
Stage 1 IGV Increase DO1 J12-7 24 VAC —
Stage 1 IGV Decrease DO2 J12-10 24 VAC —
Chiller Alarm DO3 J12-2 24 VAC Yes
Chiller Alert DO4 J12-5 24 VAC Yes
DESCRIPTION CHANNEL TERMINAL TYPE OPTIONAL
Motor Winding Temperature 1 AI1 J16-1,5 5 k —
Motor Winding Temperature 2 AI2 J16-2,6 5 k —
Motor Winding Temperature 3 AI3 J16-3,7 5 k —
Oil Sump Temperature AI5 J15-6,12 5 k —
Oil Pump Discharge Pressure (Oil Supply) AI6 J15-5 5 VDC —
Oil Sump Pressure AI7 J15-4 5 VDC —
Demand Limit Input AI8 J15-3,9 4-20 mA Yes
Refrigerant Leak Detector AI9 J15-2,8 4-20 mA Yes
IGV1 Control Signal AO1 J14-1,4 4-20 mA —
Damper Valve Feedback Fully Open DI1 J13-5 24 VAC —
Damper Valve Feedback Fully Close DI2 J13-6 24 VAC —
High Pressure Switch DI3 J13-7,3 24 VAC —
Ice Build Contact DI4 J13-8,4 24 VAC Yes
Oil Heater Relay DO1 J12-7 24 VAC —
Oil Pump Relay DO2 J12-10 24 VAC —
Economizer Damper Valve Open DO3 J12-2 24 VAC —
Economizer Damper Valve Close DO4 J12-5 24 VAC —