System information
79
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Bacnet Config
LEGEND
*Default value is shown only if configurable in this table.
NOTES:
1. The BACnet network and the device object identifier can be
modified. The default identifier has been choosen to easily rec-
ognize the Chiller on a BACnet network. The first two digits are
the BACnet CARRIER vendor number (16). These parameters
must be unique on the BACnet network. They must be modified
if more than one Carrier chillers are connected to the BACnet
network.
2. Changing one of these BACnet parameters will cause a reboot
of the board after 1 minute.
3. Changing IP address from the PIC 5 SETUP menu will require
a manual reboot or power cycle of the PIC 5 controller in order
to re-build the BACnet stack.
4. For more information, see “APPENDIX D — BACnet OPTION”
on page 98.
CCN TABLE NAME: BACNET
PIC 5 PATH: Main Menu Configuration Menu BACnet Config
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 BACnet Enable bacena 0 to 1 1 RW
2 Metric Unit bacunit 0 to 1 1 RW
3 Network network 1 to 9999 1601 RW
4 Identifier Ident 0 to 9999999 1600001 RW
RO — Read Only
RW — Read/Write