System information
75
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Reset Configuration
User Configuration
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: RESETCFG
PIC 5 PATH: Main Menu Configuration Menu Reset Configuration
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Temp Reset Type res_sel 0 to 3 0 RW
2 0 = No, 1 = 4 to 20 mA
3 2 = Remote Temp, 3 = Water DT [delta
temperature]
4 Degrees Reset At 20 mA der_20ma –30.0 to 30.0 10.0 °F RW
5 Maximum Deg Temp Reset deg_rset –30.0 to 30.0 10.0 °F RW
6 Remote Temp Full Reset remtm_fu –40.0 to 245.0 65.0 °F RW
7 Remote Temp No Reset remtm_no –40.0 to 245.0 85.0 °F RW
8 Deg Reset Water DT Full drwdt_fu –30.0 to 30.0 10.0 °F RW
9 Controlled DT Full Reset ctldt_fu 0.0 to 15.0 0.0 °F RW
10 Controlled DT No Reset ctldt_no 0.0 to 15.0 0.0 °F RW
CCN TABLE NAME: USERCONF
PIC 5 PATH: Main Menu Configuration Menu User Configuration
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 User Password use_pass 1 to 9999 1111 RW
RO — Read Only
RW — Read/Write