System information
74
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Master Slave Configuration
Prognostics Config
LEGEND
*Default value is shown only if configurable in this table.
CCN TABLE NAME: CONF_MS
PIC 5 PATH: Main Menu Configuration Menu Master Slave Config
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Slave Address slv_addr 1 to 236 2 RW
2
Master/Slave Select
0=Disable, 1=Master, 2=Slave
msl_sel 0 to 2 0 RW
3
Master Control Type
1=Local, 2=Network
3=Remote, 4=LS
ms_ctrl 1 to 4 1 RW
4
Chiller Connection Type
0=Parallel, 1=Series
ms_type 0 to 1 0 RW
5
Master Chiller Position
0=Upstream, 1=Downstream
ms_pos 0 to 1 0 RW
6
Master Lead/Lag Select
0=Lead,Lag Once Failed
1=Lead/Lag Runtime Sel
lead_sel 0 to 1 0 RW
7 Master per Capacity ms_per 25 to 75 50 % RW
8 LAG Shutdown Threshold lag_shut 25 to 75 50 % RW
9 Prestart Fault Time pref_tim 2 to 30 5 min RW
10 Unload Threshold un_th 50 to 100 100 % RW
11 Lead/Lag Balance Delta ll_bal_d 40 to 400 168 hr RW
12 Lag Start Timer lstr_tim 2 to 30 10 min RW
13 Lag Stop Timer lstp_tim 2 to 30 10 min RW
14 Lead Pulldown Time lead_pul 0 to 60 0 min RW
15 Lad Minimum Run Time lag_mini 0 to 150 0 min RW
16 Series Counter Flow serct_fl YES/NO NO RW
CCN TABLE NAME: CONF_PRG
PIC 5 PATH: Main Menu Configuration Menu Prognostics Config
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Prog Function Enable prog_en YES/NO NO RW
2 Oil Charge Completed oilch_cm YES/NO YES RW
3 Oil Filter Change Done oilfc_cm YES/NO YES RW
4 Refrigerant Charge Done refch_cm YES/NO YES RW
5 Oil Filter Pres Diff oilfl_th 0 to 420 10 psig RW
6 Oil Change Duration oilch_nt 0 to 43800 8760 hr RW
7 Trans Calib Threshold refgc_th 0 to 5 2 psig RW
8 Low Charge Cond Approach rch_cath 20 to 40 20 °F RW
9 Evap Design Approach ep_dgap 0 to 10 3 °F RW
10 Bearing Degradation beart_th 100 to 230 200 °F RW
RO — Read Only
RW — Read/Write