System information

71
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Factory Parameters
General Configuration
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: FACTORY
PIC 5 PATH: Main Menu Configuration Menu  Factory Parameters
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Chiller Type
0 = NGC, 1 = Legacy
chil_typ 0 to 1 0 RW
2 Unit Type
0 = Cool Only, 1 = Heat Machine
unit_typ 0 to 1 0 RW
3 Refrigerant Type
0 = R134a, 1 = Low Pressure
refg_typ 0 to 1 0 RW
4 Country Code coun_cod 0 to 500 86 RW
5Comp
0 = Single, 1 = Dual
comp_typ 0 to 1 1 RW
6 Condenser Type
0 = Low Pres, 1 = High Pres
cond_typ 0 to 1 0 RW
7 Chilled Medium chmedium WATER/BRINE WATER RW
8 Factory Password fac_pass 0 to 65535 4444 RW
9 Power Freq 60Hz Select freq_60h YES/NO NO RW
10 Free Coolling Option freecool YES/NO NO RW
11 VFD Option
0 = No, 1 = FS FVD, 2 = UM VFD
vfd_opt 0 to 2 0 RW
12 Hydraulic System Option hyd_opt YES/NO NO RW
13 Starter Type
0 = Full, 1 = Reduced Voltage
2 = Solid State, 3 = VFD
startype 0 to 3 0 RW
14 Motor Rated Kilowatts rkw 50 to 9999 145 kW RW
15 Low Entered Volt V1 IOB lv_enth 17 to 19 17 V RW
16 Low Exited Volt V2 IOB lv_exth 19 to 21 19 V RW
17 Heat Reclaim Option heatrecl YES/NO NO RW
18 Guide Vane1 Type
0 = Digital, 1 = Analog
gv1_type 0 to 1 0 RW
19 VFD Feedback Voltage Sel
0 = 0 to 5 V, 1 = 0 to 10 V
vfd_fdv 0 to 1 0 RW
CCN TABLE NAME: GEN_CONF
PIC 5 PATH: Main Menu Configuration Menu  General Configuration
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Stop to Start Delay min_off 1 to 15 2 min RW
2 Start to Start Delay strt_dly 4 to 45 15 min RW
3 Demand Limit Type dem_sel 0 to 1 0 RW
4 0 = Base Demand, 1 = 4 to 20 mA
5 Pulldown Ramp Type ramp_slct 0 to 1 1 RW
6 0 = Temp, 1= Load
7 Demand Limit Source DEM_SLCT 0 to 1 0 RW
8 0 = amps, 1 = kW
RO Read Only
RW Read/Write