CCN TABLE NAME: CFGLIMIT
PIC 5 PATH: Main Menu Configuration Menu  Protective Limit Config
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Condenser Freeze Point cdfreeze –20 to 35 34 °F RW
2 Evap Approach Alert evap_al 0.5 to 15 5 °F RW
3 Cond Approach Alert cond_al 0.5 to 15 6 °F RW
4 Evap Flow Delta P Cutout evap_cut 0.5 to 50 5 psig RW
5 Cond Flow Delta P Cutout cond_cut 0.5 to 50 5 psig RW
6 Cond Hi Flow DP Limit cond_val 0.5 to 50 50 psig RW
7 Cond Press Override Low cpov_lo 90 to 150 140 psig RW
8 Cond Press Override High cpov_hi 200 to 260 250 psig RW
9 Comp Discharge Alert dgt_alrt 125 to 200 200 °F RW
10 Evap Override Delta T ert_ovdt 2 to 5 3 °F RW
11 Evap Refrig Trippoint ert_trip 0 to 40 33 °F RW
12 Comp Motor Temp Override mt_over 150 to 200 200 °F RW
13 Comp Bearing Temp Alert tb_alert 155 to 175 175 °F RW
14 Comp Bearing Temp Trip tb_trip 175 to 185 185 °F RW
15 Cond Press Cutout Low cpcut_lo 155 to 160 160 psig RW
16 Cond Press Cutout High cpcut_hi 270 to 275 275 psig RW
17 Minimum Brine LWT bri_min 10 to 34 34 °F RW
18 LS Comp Bearing Alert tb_alt2 155 to 190 185 °F RW
19 LS Comp Bearing Trip tb_trip2 185 to 210 200 °F RW
20 LWT Protection Setpoint lwtp_sp 41 to 50 42.8 °F RW
21 Cond Hi Flow Alarm cond_alm DSABLE/ENABLE DSABLE RW
CCN TABLE NAME: CONF_OPT
PIC 5 PATH: Main Menu Configuration Menu  Option Configuration
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Auto Restart Option astart DSABLE/ENABLE DSABLE RW
2 Common Sensor Option commsens DSABLE/ENABLE DSABLE RW
3 Water Pressure Option wp_opt DSABLE/ENABLE DSABLE RW
4 HGBP Valve Is Configured hgbp_opt DSABLE/ENABLE DSABLE RW
5 HGBP Selection
0 = Disable, 1= Surge
2 = Low Load, 3 = Comb
hgbp_sel 0 to 3 0 RW
6 GV1 Closure at Startup gv1stpos 0.0 to 40.0 4.0 % RW
7 HGBP Open IGV1 Position hpop_gv1 0.5 to 10 5.0 % RW
8 HGBP Close IGV1 Position hgcl_gv1 1.5 to 20 10.0 % RW
9 HGBP Off DT for Low Load hgb_toff 0.5 to 10.0 4.0 ^ F RW
10 HGBP On DT for Low Load hgb_ton 0.5 to 10.0 2.0 ^ F RW
11 HGBP Low Load DB hgbp_ldb 0.5 to 2.0 1.0 ^ F RW
12 Head Pres Delta P 0% hdp_0 20.0 to 85.0 25.0 psig RW
13 Head Pres Delta P 100% hdp_100 20.0 to 85.0 50.0 psig RW
14 Head Pressure Min Output hdpv_min 0.0 to 100.0 0.0 % RW
15 Oil Temp High Threshold oil_high 100 to 140 120 ° F RW
16 Oil Temp Low Threshold oil_low 90 to 130 110 ° F RW
17 Gas Torque Factor gt_fact 0.25 to 3.0 1 ° F RW
18 Guide Vane/SRD Factor gv_srd_f 0.7 to 1.20 0.95 RW
19 Power Recovery Timeout pd_tcfg 0 to 60 15 min RW
20 Ice Build Option ice_opt DSABLE/ENABLE DSABLE RW
21 Ice Build Recycle ice_recy DSABLE/ENABLE DSABLE RW
22 Ice Build Termin Source
0 = Temp, 1 = Contact, 2 = Both
ice_term 0 to 2 0 RW
23 Refrig Leak Alarm mA leak_ma 4 to 20 20 mA RW
24 Tower Fan High Setpoint tfh_sp 55 to 105 75 RW
25 Refrigerant Leak Option leak_en DSABLE/ENABLE DSABLE RW
26 Head Pres Valve Option hdpv_opt DSABLE/ENABLE DSABLE RW