System information

64
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
Output Status
Hydraulic Status
LEGEND *Default value is shown only if configurable in this table.
CCN TABLE NAME: OUTPUTS
PIC 5 PATH: Main Menu Output Status
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Diffuser Output DIFF_OUT 4.0 to 20.0 mA RO
2 Head Pres Output HDPV_OUT 4.0 to 20.0 mA RO
3 Chiller Status Output CHST_OUT 4.0 to 20.0 mA RO
4 VFD Speed Output VFD_OUT 4.0 to 20.0 mA RO
5 Head Pres Valve Tgt Pos hdpv_tgt 0.0 to 100.0 % RO
6 Guide Vane 1 Output GV1_OUT 0.0 to 20.8 mA RO
7 Alarm Relay ALM OFF/ON OFF/ON RO
8 Alert Relay ALE OFF/ON OFF/ON RO
9 Compressor Start Relay COMP_SR OFF/ON OFF/ON RO
10 Starter Trans Sw Status TRANS OFF/ON OFF/ON RO
11 Damper Valve Close DMP_CL OFF/ON OFF/ON RO
12 Damper Valve Open DMP_OP OFF/ON OFF/ON RO
13 Guide Vane 1 Decrease GV1_DEC OFF/ON OFF/ON RO
14 Guide Vane 1 Increase GV1_INC OFF/ON OFF/ON RO
15 Hot Gas Bypass Close HGBP_OFF OFF/ON OFF/ON RO
16 Hot Gas Bypass Open HGBP_ON OFF/ON OFF/ON RO
17 Oil Heater Relay OIL_HEAT OFF/ON OFF/ON RO
18 Oil Pump Relay OIL_PUMP OFF/ON OFF/ON RO
19 Tower Fan Relay High TFR_HIGH OFF/ON OFF/ON RO
20 Tower Fan Relay Low TFR_LOW OFF/ON OFF/ON RO
21 Damper Valve Tgt Pos dmp_tgt 0 to 2 RO
22 0=Close,1=Hold, 2=Open RO
23 HGBP Valve Tgt Pos hgbp_tgt 0 to 2 RO
24 0=Close,1=Hold, 2=Open RO
CCN TABLE NAME: HYDRLIC
PIC 5 PATH: Main Menu Hydraulic Status
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Condenser Water Flow CDW_FLOW NO/YES RO
2 Chilled Water Pump CHWP OFF/ON RO
3 Cond Entering Water Pres COND_EWP –6.7 to 420.0 psig RO
4 Cond Leaving Water Pres COND_LWP –6.7 to 420.0 psig RO
5 Condenser Water Delta P cdw_pd –6.7 to 420.0 psig RO
6 Cond Water Pulldown/Min cdw_pull –20 to 20.0 °F RO
7 Condenser Water Pump CDWP OFF/ON RO
8 Chilled Water Flow CHW_FLOW NO/YES RO
9 Evap Enter Water Pres EVAP_EWP –6.7 to 420.0 psig RO
10 Evap Leaving Water Pres EVAP_LWP –6.7 to 420.0 psig RO
11 Chilled Water Delta P chw_pd –6.7 to 420.0 psig RO
12 Chilled Water Pulldown/Min chw_pull –20 to 20.0 °F RO
13 Tower Fan Relay High TFR_HI OFF/ON RO
14 Tower Fan Relay Low TFR_LO OFF/ON RO
15 Controlled Water DT ctrlw_dt –40.0 to 245.0 °F RO
16 Cond Water Flow Status cdw_fl_s 0 to 2 RO
17 0=Fail or Not Started
18 1=Success, 2=Verifying
19 Evap Water Flow Status chw_fl_s 0 to 2 RO
20 0=Fail or Not Started
21 1=Success, 2=Verifying
22 Pumpdown/Lockout State pdown_st 0 to 255 RO
RO Read Only
RW Read/Write