System information

61
APPENDIX A — PIC 5 SCREEN AND TABLE STRUCTURE (cont)
GENERAL PARAMETERS
LEGEND
*Default value is shown only if configurable in this table.
†0 = OFF
1 = CTLTEST
2 = PUMPDOWN
3 = LOCKOUT
4 = RECYCLE
5 = TRIPOUT
6 = TIMEOUT
7 = PRESTART
8 = STARTUP
9 = AUTORST
10 = RAMPING
11 = RUNNING
12 = OVERRIDE
13 = DEMAND
14 = SHUTDOWN
**RW from network.
CCN TABLE NAME: GENUNIT
PIC 5 PATH: Main Menu General Parameters
LINE PIC 5 DESCRIPTION CCN NAME RANGE
DEFAULT
VALUE*
UNIT READ/WRITE
1 Control Mode ctl_mode 0 to 3 RO
2 0 = Local, 1 = Network
3 2 = Remote, 3 = Local Sched
4 Compressor1 Run Status cm_stas1 0-14† RO
5 Deter Start Stop Command stat/stop RO
6 Network: Cmd Start/Stop CHIL_S_S 0 to 1 RW**
7 Network:Cmd Occupied CHIL_OCC 0 to 1 RW**
8 Cooling / Heating Select HC_SEL COOL/HEAT COOL RW
9 Control Point CTRL_PNT 10.0 to 160.0 °F RW**
10 Control Point Reset reset –30.00 to 30.00 °F RO
11 Actual Setpoint setpoint 10.0 to 150.0 °F RO
12 Percent Load Current amps_p 0.0 to 999.0 % RO
13 Active Demand Limit DEM_LIM 10.0 to 100.0 100 % RW**
14 Emergency Stop EMSTOP 0 to 1 0 RW**
15 Chiller State Number ch_state 0 to 500 RO
16 Chiller Run Status ch_stat 0 to 2 RO
17 0 = OFF, 1 = READY, 2 = ON
18 Local Schedule Occupied loc_occ NO/YES RO
19 Ice Schedule Occupied ice_occ NO/YES RO
20 MS Start Stop Command ms_stsp STOP/START RO
21 Remote Reset Alarm REM_RST YES/NO RO
22 Stop Override STP_OVER YES/NO NO RW
RO Read Only
RW Read/Write