System information
32
Table 15 — PIC 5 Alarm Codes (cont)
ALARM
CODE
(ALARMRST)
ALARM TEXT
DESCRIPTION
RESET TYPE
ACTION TAKEN BY
CONTROL
POSSIBLE CAUSE
TEMPERATURE SENSOR FAULTS (CONT)
Alm-208
ALM-208 Sensor Fault —
Low Speed Motor End
Bearing Temp
Automatic if the temperature mea-
sured by the sensor returns to normal
Unit shuts down
Check sensor resistance.
Check for proper wiring between
low speed motor end bearing tem-
perature sensor and IOB connector.
Check for disconnected, grounded,
or shorted wiring.
Check IOB channel type configura-
tions.
Alm-209
ALM-209 Sensor Fault —
Low Speed Comp End
Bearing Temp
Automatic if the temperature mea-
sured by the sensor returns to normal
Unit shuts down
Check sensor resistance.
Check for proper wiring between
low speed compressor end bearing
temperature sensor and IOB con-
nector. Check for disconnected,
grounded, or shorted wiring.
Check IOB channel type configura-
tions.
Alm-210
ALM-210 Sensor Fault —
High Speed Motor End
Bearing Temp
Automatic if the temperature mea-
sured by the sensor returns to normal
Unit shuts down
Check sensor resistance.
Check for proper wiring between
high speed motor end bearing tem-
perature sensor and IOB connector.
Check for disconnected, grounded,
or shorted wiring.
Check IOB channel type configura-
tions.
Alm-211
ALM-211 Sensor Fault —
High Speed Comp End
Bearing Temp
Automatic if the temperature mea-
sured by the sensor returns to normal
Unit shuts down
Check sensor resistance.
Check for proper wiring between
high speed compressor end bearing
temperature sensor and IOB con-
nector. Check for disconnected,
grounded, or shorted wiring.
Check IOB channel type configura-
tions.
Alm-212
ALM-212 Sensor Fault —
Compressor Motor
Temp 1
Automatic if the temperature mea-
sured by the sensor returns to normal
Unit shuts down
Check sensor resistance.
Check for proper wiring between
compressor motor temp 1 sensor
and IOB connector. Check for dis-
connected, grounded, or shorted
wiring.
Check IOB channel type configura-
tions.
Alm-213
ALM-213 Sensor Fault —
Compressor Motor
Temp 2
Automatic if the temperature mea-
sured by the sensor returns to normal
Unit shuts down
Check sensor resistance.
Check for proper wiring between
compressor motor temp 2 sensor
and IOB connector. Check for dis-
connected, grounded, or shorted
wiring.
Check IOB channel type configura-
tions.
Alm-214
ALM-214 Sensor Fault —
Compressor Motor
Temp 3
Automatic if the temperature mea-
sured by the sensor returns to normal
Unit shuts down
Check sensor resistance.
Check for proper wiring between
compressor motor temp 3 sensor
and IOB connector. Check for dis-
connected, grounded, or shorted
wiring.
Check IOB channel type configura-
tions.