System information

22
Table 11 — Pre-Start Alerts and Alarms
*Evap trip point = 33 F (0.6 C) (water) or EVAP REFRIG TRIPPOINT
(brine).
The compressor RUN STATUS parameter on the default
screen line now reads PRESTART. If a test is not successful,
the start-up is delayed or aborted. If the tests are successful, the
chilled water pump relay energizes, and the main screen line
now reads STARTUP.
START-UP One second after the successful pre-start check,
the chilled water and condenser water pump relays are ener-
gized.
Five seconds later, the control monitors the chilled water
and condenser water flow devices and waits until the WATER
FLOW VERIFY TIME (service-configured, default 5 minutes)
expires to confirm water flow.
After water flow is verified, the water temperature is com-
pared to CONTROL POINT +
1
/
2
CHILLED WATER DEAD-
BAND. If the temperature is less than or equal to this value, the
control turns off the condenser pump relay and goes into RE-
CYCLE mode.
If the RECYCLE condition does not exist, the start-up se-
quence continues and checks the guide vane position. For a sin-
gle-stage compressor (Comp [Single = 0, Dual = 1] = 0 in
FACTORY configuration), if the guide vanes are more than
4% open, the start-up waits until the controller closes the vanes.
For a dual-stage compressor (Comp [Single = 0, Dual = 1] = 1
in FACTORY configuration), the guide vanes are opened to the
initial position specified with GV1 Closure at Startup in the
Option Configuration menu.
If an HGBP or economizer damper valve is equipped and
enabled, the control checks that the position of these valves is
fully closed.
If the vanes and valves position are verified and the oil
pump pressure is less than 4 psi (27.6 kPa), the oil pump relay
is energized.
The control then waits until the oil pressure (OIL PRESS
VERIFY TIME, operator-configured, default 40 seconds)
reaches a maximum of 18 psi (124 kPa). After oil pressure is
verified, the control waits 40 seconds for oil prelube, and the
compressor start relay energizes to start the compressor.
Chiller Shutdown Sequence — Chiller shutdown
begins if any of the following occurs:
Local OFF button is pressed
A recycle condition is present (see the previous section)
The time schedule has gone into unoccupied mode
The chiller protective limit has been reached and chiller
is in alarm
The start/stop status (CHIL_S_S) is overridden to stop
from the network
If the chiller is normally shut down from running, a soft-
stop shutdown will be performed. The soft-stop feature closes
the guide vanes of the compressor automatically if a non-alarm
stop signal occurs before the compressor motor is deenergized.
Any time the compressor is directed to STOP (except in the
cases of a fault shutdown), the guide vanes are directed to close
and VFD will be commanded to minimum speed for a variable
speed compressor. The compressor shuts off when any of the
following is true:
AVERAGE LINE CURRENT (%) drops below the
SOFT STOP AMPS THRESHOLD
ACTUAL GUIDE VANE POSITION drops below 4%
Four minutes have elapsed since the stop was initialized
When any of these conditions is true, the shutdown se-
quence stops the compressor by deactivating the compressor
start relay. The guide vanes are then commanded to the fully
closed position. The oil pump relay will be turned off after 60
seconds post-lube.
Finally, the chilled water/brine pump and condenser water
pump are shut down.
Oil Lubrication Control — As part of the pre-start
checks executed by the controls, the oil sump temp is com-
pared to the evaporator saturated refrigerant temperature. If the
oil temperature is less than 140 F (60 C) and less than evapora-
tor saturated refrigerant temperature plus 50° F (27.8° C), the
start-up will be delayed until either of these conditions is no
longer true. Once this temperature is confirmed, the start-up
continues.
The oil heater relay is energized whenever the chiller com-
pressor is off and the oil sump temperature is less than 140 F
(60 C) or the oil sump temperature is less than the evaporator
saturated refrigerant temperature plus 53° F (29.4° C). The oil
heater is turned off when either of the following conditions is
true:
Oil sump temperature is more than 152 F (66.7 C)
Oil sump temperature is more than 144° F (62.2 C) and
more than the evaporator saturated refrigerant tempera-
ture plus 55° F (30.6° C).
The oil heater is always off when the compressor is running.
The oil pump is also energized for 30 seconds after each 30
minutes of the oil heat relay being energized in order to stir the
oil for more evenly distributed heating.
Control Points
SET POINT The set point can be configured at the Setpoint
menu (“USER” access level).
The set point is determined by the heat/cool mode, EWT
PRE-START ALERT
CONDITION
STATE
NO.
ALARM
OR
ALERT
STARTS IN 12 HOURS >= 8 100 Alert
OIL SUMP TEMP <= 140 F (60 C) AND OIL
SUMP TEMP <= EVAP_SAT + 50 F (27.8 C)
101 Alert
CONDENSER PRESSURE >=
COND PRESS OVERRIDE – 20 psi
102 Alert
Number of recycle restart in the last 4 hours is
greater than 5
103 Alert
COMP BEARING TEMP >= COMP BEARING
ALERT– 10 F (5.5 C)
230 Alarm
COMP MOTOR WINDING TEMP >= MOTOR
TEMP OVERRIDE – 10 F (5.5 C)
231 Alarm
COMP DISCHARGE TEMP >= COMP DIS-
CHARGE ALERT– 10 F (5.5 C)
232 Alarm
EVAP_SAT < Evap trip point* +
EVAP OVERRIDE DELTA T
or
EVAP REFRIG LIQUID TEMP < Evap trip
point* + EVAP OVERRIDE DELTA T
233 Alarm
AVERAGE LINE VOLTAGE <=
UNDERVOLTAGE THRESHOLD
234 Alarm
AVERAGE LINE VOLTAGE >=
OVERVOLTAGE THRESHOLD
235 Alarm
Guide vane 1 has not been calibrated success-
fully
236 Alarm