System information

109
APPENDIX D — BACnet OPTION (cont)
Table C — BACnet Point Table (cont)
LEGEND
*Object names are built from CCN table name and CCN point name
combined for easy recognition.
POINT DESCRIPTION
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT
ID
BACNET OBJECT NAME*
Surge Protection Active
RO NO NO/YES AV:121 MAISURGE_surg_pro
Surge Protection Counts
RO AV:120 MAISURGE_spc
Surge Region
No=0,Low=1,High=2
RO 0 to 2 AV:113 MAISURGE_act_reg
Surge Time Period
RO min 8 7 to 10 AV:269 CFGSURGE_surge_t
Swift Restart Active
RO NO NO/YES BV:72 MAISWRST_sw_rst
Target GV1 Pos
RO % 0.0 AV:111 CAPACTRL_gv1_tgt
Target VFD Speed
RO % 0.0 AV:112 CAPACTRL_vfd_tgt
Temp Ramp Rate F/Min
RO ^F 3 1 to 10 AV:242 SERVICE1_tmramprt
Temp Reset Type
No=0,4~20ma=1
Remote Temp=2,Water DT=3
RO 0 to 3 AV:7 RESETCFG_res_sel
Total Compressor Starts
RO 0 0 to 99999 AV:98 RUNTIME_C_STARTS
Tower Fan High Setpoint
75 55 TO 105 AV:319 CONF_OPT_tfh_sp
Tower Fan Relay High
RO OFF OFF/ON BV:38 OUTPUTS_TFR_HIGH
Tower Fan Relay Low
RO OFF OFF/ON BV:39 OUTPUTS_TFR_LOW
Trans Calib Threshold
RO AV:337 CONF_PRG_refgc_th
Under Volt Start Delay
RO sec 1 AV:189 ISM_MCFG_uvs_del
Undervoltage Threshold
RO % 85 85 to 95 AV:187 ISM_MCFG_udvol_th
Unit is Lead or Lag
0=Disable,1=Lead,2=Lag
RO 0 0 to 2 AV:196 MAIN_MS_lead_lag
Unit is Master or Slave
0=Disable, 1=Master, 2=Slave
RO 0 0 to 2 AV:195 MAIN_MS_mst_slv
Unit Type
Cool Only=0,Heat Mach=1
RO 0 0 to 1 AV:210 FACTORY_unit_typ
Unload Threshold
RO % 100 50 to 100 AV:329 CONF_MS_un_th
User Password
RO AV:6 USERCONF_use_pass
VDO High Lift Load Line
RO ^F 0.0 0.0 to 200.0 AV:48 TEMP_LIFT_1
VDO High Lift Load Line
RO ^F 0.0 AV:164 MAIN_SRD_lift_1
VDO Logic Start Delay
RO min 0.0 AV:166 MAIN_SRD_strt_tmr
VDO Low Lift Load Line
RO ^F 0.0 0.0 to 200.0 AV:49 TEMP_LIFT_2
VDO Low Lift Load Line
RO ^F 0.0 AV:165 MAIN_SRD_lift_2
VFD Current Actual mA
RO mA 0.00 AV:76 INPUTS_VFDC_MA
VFD Current Limit
RO amp 250 0.0 to 99999.0 AV:229 CONF_VFD_vfdculm
VFD Feedback Voltage Sel
0=0~5V 1=0~10V
RO 0 0 to 1 AV:223 FACTORY_vfd_fdv
VFD Gain
RO 0.75 0.10 to 1.50 AV:224 CONF_VFD_vfd_gain
VFD Load Current
RO amp 0.0 AV:145 POWER_VFD_LOAD
VFD Load Current 20mA
RO amp 200.0 10.0 to 5000.0 AV:230 CONF_VFD_vfdc20ma
VFD Load Factor
RO 0.000 AV:144 POWER_VFD_FACT
VFD Maximum Speed
RO % 100.0 90.0 to 110.0 AV:225 CONF_VFD_vfd_max
VFD Minimum Speed
RO
% 70 65.0 to 100.0 AV:226 CONF_VFD_vfd_min
VFD Option
No =0,FS VFD=1,UM VFD=2
RO 0 0 to 2 AV:217 FACTORY_vfd_opt
VFD Speed @Shutdown
RO % 0.0 0 to 100 AV:191 MAISWRST_vfd_shut
VFD Speed Feedback
RO V 0.0 AV:74 INPUTS_VFD_IN
VFD Speed Output mA
RO mA 4.0 4.0 to 20.0 AV:80 OUTPUTS_VFD_OUT
VFD Speed Step Surge
RO % 1.5 1.0 to 5.0 AV:264 CFGSURGE_vfdstpsg
VFD Start Speed
RO % 80.0 65.0 to 100.0 AV:227 CONF_VFD_vfd_str
VFD Surge Line Gain
RO 2.0 2.0 to 3.5 AV:228 CONF_VFD_vfd_slg
Volt Transformer Ratio:1
RO 1 1 to 115 AV:178 ISM_MCFG_vt_rat
Voltage Umbal Persist
RO 5 sec 1 to 10 AV:80 ISM_MCFG_vu_per
Voltage Umbal Threshold
RO % 5 1 to 10 AV:176 ISM_MCFG_vu_th
Water Flow Verify Time
RO min 5.0 0.5 to 5.0 AV:250 SERVICE1_wflow_t
Water Pressure Option
RO DSABLE DSABLE/ENABLE BV:92 CONF_OPT_wp_opt
AV Analog Value
BV Binary Value
RO Read Only
RW Read Write