System information
108
APPENDIX D — BACnet OPTION (cont)
Table C — BACnet Point Table (cont)
LEGEND *Object names are built from CCN table name and CCN point name
combined for easy recognition.
POINT DESCRIPTION
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT
ID
BACNET OBJECT NAME*
Recycle Shutdown Delta T
RO ^F 1.0 0.5 to 4.0 AV:244 SERVICE1_rcysh_dt
Refrig Leak Alarm mA
RO Ma 20 4 to 20 AV:318 CONF_OPT_leak_ma
Refrig Leak Sensor
RO mA 0.0 AV:71 INPUTS_REF_LEAK
Refrigerant Leak Option
RO DSABLE DSABLE/ENABLE BV:96 CONF_OPT_leak_en
Refrigerant Type
R134a=0,Low Pressure=1
RO 0 0 to 1 AV:211 FACTORY_refg_typ
Remote Contact
RO OPEN OPEN/CLOSE BV:17 INPUTS_REM_CON
Remote Reset Alarm
RO 0 0 to 1 BV:8 GENUNIT_REM_RST
Remote Reset Sensor
RO °F 0.0 –40.0 to 245 AV:50 TEMP_R_RESET
Remote Temp Full Reset
RO ^F 10.0 –30.0 to 30.0 AV:10 RESETCFG_remtm_fu
Remote Temp No Reset
RO °F 65.0 –40.0 to 245 AV:11 RESETCFG_remtm_no
Series Counter Flow
RO NO YES/NO BV:98 CONF_MS_serct_fl
Service Ontime
RO hour 0.0 0 to 500000.00 AV:100 RUNTIME_SRV_HRS
Service Password
RO 2222 0 to 9999 AV:232 SERVICE1_ser_pass
Single Cycle Dropout
RO DSABLE DSABLE/ENABLE BV:67 ISM_MCFG_scycd_en
Slave Address
RO 2 1 to 236 AV:320 CONF_MS_slv_addr
Slave Control Type
0=Local, 1=Network
2=Remote,3=Local Sched
RO 0 0 to 3 AV:198 MAIN_MS_sl_ctrl
Soft Stop Amps Threshold
RO % 70 40 to 100 AV:249 SERVICE1_sf_st_th
Spare Safety Input
RO OPEN OPEN/CLOSE BV:21 INPUTS_SAFETY
SRD IGV Offset Select
RO 3 1 to 5 AV:290 CONF_SRD_off_sel
SRD Pos Load @25%
RO % 73.5 0.0 to 100.0 AV:296 CONF_SRD_srd1_25
SRD Pos Load @50%
RO % 35.1 0.0 to 100.0 AV:297 CONF_SRD_srd1_50
SRD Pos Load @75%
RO % 19.5 0.0 to 100.0 AV:298 CONF_SRD_srd1_75
SRD Position @Shutdown
RO % 0.0 0 to 100 AV:190 MAISWRST_srd_shut
SRD Rotating Stall Alarm
RO NO NO/YES BV:64 MAIN_SRD_diff_alm
SRD Stall Closure Time
RO min 0.0 AV:167 MAIN_SRD_stalltmr
Start to Start Delay
RO min 15 4 to 45 AV:2 GENCONF_strt_dly
Start to Start Timer
RO min 0.0 4.0 to 45.0 AV:102 RUNTIME_stst_tim
Starter Fault Feedback
RO OPEN OPEN/CLOSE BV:22 INPUTS_STARTFLT
Starter LRA Rating
RO amp 2000 100 to 65535 AV:173 ISM_MCFG_str_lra
Starter Trans Sw Status
RO OFF OFF/ON BV:29 OUTPUTS_TRANS
Starter Type
0=Full Volt 1=Redu Volt
2=Solid State 3=FS VFD
RO 0 0 to 3 AV:169 ISM_MCFG_star_typ
Starter Type
Full=0,Reduced Voltage=1
Solid State=2,VFD=3
RO 0 0 to 3 AV:218 FACTORY_startype
Starts In 12 Hours
RO 0 0 to 8 AV:97 RUNTIME_ST_CNT12
Stop Override
RO 0 0 to 1 BV:9 GENUNIT_STP_OVER
Stop to Start Delay
RO min 2 1 to 15 AV:1 GENCONF_min_off
Stop to Start Timer
RO min 0.0 1.0 to 15.0 AV:101 RUNTIME_spst_tim
Surge Counts
RO 0 AV:118 MAISURGE_sc
Surge Deadband
RO ^F 1.5 0.5 to 3.0 AV:258 CFGSURGE_sghg_db
Surge Delay Time
RO sec 15 0 to 120 AV:268 CFGSURGE_surg_del
Surge Delta Amps %
RO % 20 5 to 40 AV:262 CFGSURGE_surge_a
Surge IGV1 Max Pos
RO AV:255 CFGSURGE_gv1_smax
Surge IGV1 Min Pos
RO AV:256 CFGSURGE_gv1_smin
Surge Line High Offset
RO ^F 1.5 0.1 to 3.0 AV:259 CFGSURGE_sgl_hoff
Surge Line Offset
RO ^F 2.0 1.0 to 3.0 AV:257 CFGSURGE_sgl_off
Surge Line Shape Factor
RO AV:260 CFGSURGE_sgl_shpf
Surge Line Speed Factor
RO 2.00 0.00 to 3.00 AV:261 CFGSURGE_sgl_spdf
Surge Prevention Active
RO NO NO/YES AV:119 MAISURGE_surg_act
AV — Analog Value
BV — Binary Value
RO — Read Only
RW — Read Write