System information
107
APPENDIX D — BACnet OPTION (cont)
Table C — BACnet Point Table (cont)
LEGEND *Object names are built from CCN table name and CCN point name
combined for easy recognition.
POINT DESCRIPTION
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT
ID
BACNET OBJECT NAME*
Motor Percent Kilowatts
RO % 0.0 AV:139 POWER_KW_P
Motor Rated Kilowatts
RO kW 145 50 to 9999 AV:219 FACTORY_rkw
Motor Rated Line Voltage
RO V 460 200 to 13800 AV:174 ISM_MCFG_rlv
Motor Rated Load Amps
RO amp 200 10 to 5000 AV:170 ISM_MCFG_rla
MS Start Stop Command
RO STOP START/STOP BV:7 GENUNIT_ms_stsp
Network:Cmd Occupied
RO BV:3 GENUNIT_CHIL_OCC_rd
Network:Cmd Occupied
RW 0 to 1 BV:105 GENUNIT_CHIL_OCC_wr
Network:Cmd Start/Stop
RO BV:2 GENUNIT_CHIL_S_S_rd
Network:Cmd Start/Stop
RO 0 0 to 1 BV:75 MAIN_MS_lag_s_s
Network:Cmd Start/Stop
RW 0 to 1 BV:103 GENUNIT_CHIL_S_S_wr
Oil Change Duration
RO hr 8760 0 to 43800 AV:336 CONF_PRG_oilch_nt
Oil Filter Pres Diff
RO psig 10 0 to 420 AV:335 CONF_PRG_oilfl_th
Oil Heater Relay
RO ON OFF/ON BV:36 OUTPUTS_OIL_HEAT
Oil Press Verify Time
RO sec 40 15 to 300 AV:248 SERVICE1_oilpvr_t
Oil Pump Delta P
RO ^psig 0.0 –6.7 to 420.0 AV:56 PRESSURE_OIL_PD
Oil Pump Relay
RO OFF OFF/ON BV:37 OUTPUTS_OIL_PUMP
Oil Sump Pressure
RO psig –10.0 –6.7 to 420.0 AV:55 PRESSURE_OILP_SMP
Oil Sump Temp
RO °F 0.0 –40.0 to 245 AV:45 TEMP_OILT_SMP
Oil Supply Pressure
RO psig –10.0 –6.7 to 420.0 AV:54 PRESSURE_OILP_DIS
Oil Supply Temp
RO °F 0.0 –40.0 to 245 AV:46 TEMP_OILT_DIS
Over Under Volt Persist
RO sec 5 1 to 10 AV:188 ISM_MCFG_ovud_per
Overrid Act Demand Limit
RO % 100 10 to 100.0 AV:208 MAIN_MS_demlimov
Overrid Control Point
RO °F 45.0 10 to 160.0 AV:207 MAIN_MS_ctrpntov
Overvoltage Threshold
RO % 115 105 to 115 AV:186 ISM_MCFG_ovvol_th
Peak Detection Channel
RO 0 0 to 10 AV:303 CONF_SRD_peak_ch3
Peak Detection Threshold
RO V 0.0000 0.0000 to 5.0000 AV:302 CONF_SRD_peak_th
Percent Line Voltage
RO % 0.0 AV:137 POWER_VOLT_P
Percent Load Current
RO % 0.0 0.0 to 999.0 AV:21 GENUNIT_amps_p
Percent Load Current
RO % 0.0 AV:129 POWER_AMPS_P
Phase 1 Faulted
RO NO NO/YES BV:60 MAIISMH_phase_h1
Phase 2 Faulted
RO NO NO/YES BV:61 MAIISMH_phase_h2
Phase 3 Faulted
RO NO NO/YES BV:62 MAIISMH_phase_h3
Power Down Active
RO NO NO/YES BV:70 MAISWRST_power_dn
Power Factor
RO 0.000 AV:142 POWER_POW_FACT
Power Freq 60Hz Select
RO NO YES/NO BV:83 FACTORY_freq_60h
Power Recovery Duration
RO min 0.4 0 to 1 AV:194 MAISWRST_pd_dur
Power Recovery Timeout
RO min 15 0 to 60 AV:316 CONF_OPT_pd_tcfg
Prestart Fault Time
RO min 0 to 30 AV:203 MAIN_MS_preflt
Prestart Fault Timer
RO min 5 2 to 30 AV:328 CONF_MS_pref_tim
Prog Function Enable
RO NO YES/NO BV:99 CONF_PRG_prog_en
Proportional Dec Band
RO 6.0 2.0 to 10.0 AV:236 SERVICE1_gv1decdb
Proportional Inc Band
RO 6.5 2.0 to 10.0 AV:237 SERVICE1_gv1incdb
Pulldown Ramp Type
0 = Temp, 1 = Load
RO 1 0 to 1 AV:4 GENCONF_rampslct
Pulldown Time
RO min 0 to 30 AV:204 MAIN_MS_pulltime
Pulldown: Delta T / Min
RO ^F 0 -0 to 100 AV:205 MAIN_MS_pull_dt
Pumpdown/Lockout State
RO 0 to 255 AV:96 HYDRLIC_pdown_st
Recovery Start Request
RO BV:76 MAIN_MS_lag_rec
Recy Startup In 4 Hours
RO 0 0 to 6 AV:103 RUNTIME_RCYSTCNT
Recycle Restart Delta T
RO ^F 5.0 2.0 to 10.0 AV:245 SERVICE1_rcyst_dt
AV — Analog Value
BV — Binary Value
RO — Read Only
RW — Read Write