System information

106
APPENDIX D — BACnet OPTION (cont)
Table C — BACnet Point Table (cont)
LEGEND *Object names are built from CCN table name and CCN point name
combined for easy recognition.
POINT DESCRIPTION
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT
ID
BACNET OBJECT NAME*
Line Frequency Faulting
RO Hz 0.0 AV:141 POWER_LN_FREQ
Line Frequency Faulting
RO Hz 0.0 AV:149 MAIISMH_FREQ_H
Line Frequency Faulting
RO DSABLE DSABLE/ENABLE BV:68 ISM_MCFG_lfref_en
Line Voltage Phase 1
RO V 0.0 AV:133 POWER_LN_VOLT1
Line Voltage Phase 1
RO V 0.0 AV:156 MAIISMH_VOLT_H1
Line Voltage Phase 2
RO V 0.0 AV:134 POWER_LN_VOLT2
Line Voltage Phase 2
RO V 0.0 AV:157 MAIISMH_VOLT_H2
Line Voltage Phase 3
RO V 0.0 AV:135 POWER_LN_VOLT3
Line Voltage Phase 3
RO V 0.0 AV:158 MAIISMH_VOLT_H3
Local Schedule Occupied
RO NO NO/YES BV:5 GENUNIT_loc_occ
Local=0,Network=1
RO 1601 1 to 9999 AV:341 BACNET_network
Locked Rotor Start Delay
RO cycles 5 1 to 10 AV:172 ISM_MCFG_lrs_del
Low Charge Cond Approach
RO °F 20 20 to 40 AV:338 CONF_PRG_rch_cath
Low DSH Override Flag
RO NO NO/YES BV:51 OVERRIDE_dshov_fl
Low Entered Volt V1 IOB
RO V 17 17 to 19 AV:220 FACTORY_lv_enth
Low Exited Volt V2 IOB
RO V 19 19 to 21 AV:221 FACTORY_lv_exth
Low Lift Load @25%
RO ^F 27.2 0.0 to 100.0 AV:301 CONF_SRD_lf2_25
Low Lift Profile Select
RO 3 1 to 5 AV:291 CONF_SRD_pro_sel
Low Sour Temp Over Flag
RO NO NO/YES BV:56 OVERRIDE_lstov_fl
Low SST Override Flag
RO NO NO/YES BV:53 OVERRIDE_sstov_fl
LS Comp Bearing Alert
RO °F 185 155 to 190 AV:287 CFGLIMIT_tb_alt2
LS Comp Bearing Temp
RO °F 0.0 –40.0 to 245 AV:39 TEMP_MTRB2
LS Comp Bearing Trip
RO °F 200 185 to 210 AV:288 CFGLIMIT_tb_trip2
LS Motor Bearing Temp
RO °F 0.0 –40.0 to 245 AV:38 TEMP_MTRB1
LWT Protection Setpoint
RO °F 42.8 41 to 50 AV:289 CFGLIMIT_lwtp_sp
Master Chiller Position
0=Upstream, 1=Downstream
RO 0 0 to 1 AV:324 CONF_MS_ms_pos
Master Chiller Running
RO 0 0 to 1 BV:80 MAIN_MS_MST_RUN
Master Control Type
0=Local, 1=Network
2=Remote,3=Local Sched
RO 0 0 to 3 AV:197 MAIN_MS_ms_ctrl
Master Control Type
1=Local, 2=Network
3=Rem, 4= LS
RO 1 1 to 4 AV:322 CONF_MS_ms_ctrl
Master Lead Lag Select
0=Lead, Lag Once Failed
1=Lead/Lag Runtime Sel
RO 0 0 to 1 AV:325 CONF_MS_lead_sel
Master per Capacity
RO % 50 25 to 75 AV:326 CONF_MS_ms_per
Master/Slave Ctrl Active
RO BV:73 MAIN_MS_ms_act
Master/Slave Select
0=Disable
1=Master, 2=Slave
RO 0 0 to 2 AV:321 CONF_MS_msl_sel
Max Amps Change Value
RO % 0.0 AV:117 MAISURGE_amch_max
Maximum Deg Temp Reset
RO ^F 10.0 –30.0 to 30.0 AV:9 RESETCFG_deg_rset
Maximum GV Movement
RO % 2.0 2.0 to 4.0 AV:252 SERVICE1_max_gv
Maximum Pressure Ratio
RO 3.0000 1.0000 to 5.0000 AV:265 CFGSURGE_pr_max
MBB Power Calibration
RO 0.970 0.900 to 1.000 AV:251 SERVICE1_mbb_pfcl
Metric Unit
RO 1 0 to 1 BV:101 BACNET_bacunit
Minimum Brine LWT
RO °F 34 10 to 34 AV:286 CFGLIMIT_bri_min
Minimum Pressure Ratio
RO 1.5000 1.0000 to 5.0000 AV:266 CFGSURGE_pr_min
Motor Actual Frequency
RO Hz 0.0 AV:143 POWER_MOT_FREQ
Motor Current CT Ratio:1
RO 100 3 to 1000 AV:177 ISM_MCFG_ct_ratio
Motor Kilowatts
RO kW 0.0 AV:138 POWER_KW
Motor Kilowatts Hours
RO kW 0.0 AV:140 POWER_KWH
Motor Locked Rotor Trip
RO amp 1000 100 to 65535 AV:171 ISM_MCFG_mot_lra
AV Analog Value
BV Binary Value
RO Read Only
RW Read Write