APPENDIX D — BACnet OPTION (cont)
Table C — BACnet Point Table (cont)
LEGEND *Object names are built from CCN table name and CCN point name
combined for easy recognition.
POINT DESCRIPTION
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT
ID
BACNET OBJECT NAME*
HGBP Valve Status
Cl=0,Inter=1,Op=2,Fail=3
RO 1 0 to 3 AV:64 INPUTS_HGBP_ACT
HGBP Valve Tgt Pos
0=CL,1=Hold,2=Open
RO 1 0 to 2 AV:84 OUTPUTS_hgbp_tgt
High Bearing Temp Over
RO NO NO/YES BV:55 OVERRIDE_tbov_fl
High Lift Load @100%
RO ^F 67.5 0.0 to 100.0 AV:299 CONF_SRD_lf1_100
High Lift Load @25%
RO ^F 52.4 0.0 to 100.0 AV:300 CONF_SRD_lf1_25
High Lift Override Flag
RO NO NO/YES BV:52 OVERRIDE_lftov_fl
High Motor Current Flag
RO NO NO/YES BV:58 OVERRIDE_ampov_fl
High Motor Temp Over
RO NO NO/YES BV:54 OVERRIDE_mtov_fl
High Pressure Switch
RO OPEN OPEN/CLOSE BV:16 INPUTS_HP_SW
High VFD Current
RO NO NO/YES BV:59 POWER_VFDC_HI
Hot Gas Bypass Close
RO OFF OFF/ON BV:34 OUTPUTS_HGBP_OFF
Hot Gas Bypass Open
RO OFF OFF/ON BV:35 OUTPUTS_HGBP_ON
HS Comp Bearing Temp
RO °F 0.0 –40.0 to 245 AV:41 TEMP_MTRB4
HS Motor Bearing Temp
RO °F 0.0 –40.0 to 245 AV:40 TEMP_MTRB3
Hydraulic System Option
RO NO YES/NO BV:85 FACTORY_hyd_opt
I2T Sum Heat Phase 1
RO % 0.0 AV:153 MAIISMH_sum1ht_h
I2T Sum Heat Phase 2
RO % 0.0 AV:154 MAIISMH_sum2ht_h
I2T Sum Heat Phase 3
RO % 0.0 AV:155 MAIISMH_sum3ht_h
Ice Build Contact Closed
RO OPEN OPEN/CLOSE BV:19 INPUTS_ICE_CON
Ice Build Option
RO DSABLE DSABLE/ENABLE BV:94 CONF_OPT_ice_opt
Ice Build Recycle
RO DSABLE DSABLE/ENABLE BV:95 CONF_OPT_ice_recy
Ice Build Setpoint
RW °F 40.0 15.0 to 60.0 AV:345 SETPOINT_ice_sp
Ice Build Termin Source
0=Temp,1=Contact,2=Both
RO 0 0 to 2 AV:317 CONF_OPT_ice_term
Ice Schedule Occupied
RO NO NO/YES BV:6 GENUNIT_ice_occ
Identifier
RO 1600001 0 to 9999999 AV:342 BACNET_ident
ISM Config Conflict
RO NO NO/YES BV:65 ISM_MCFG_ism_cflt
ISM Trip Relay Status
RO OPEN OPEN/CLOSE BV:24 INPUTS_TRIPR
Lag Minimum Running Time
RO min 0 0 to 150 AV:334 CONF_MS_lag_mini
LAG Shutdown Threshold
RO % 50 25 to 75 AV:327 CONF_MS_lag_shut
LAG Start Time
RO min 0 0 to 60 AV:201 MAIN_MS_lagstart
Lag Start Timer
RO min 10 2 to 30 AV:331 CONF_MS_lstr_tim
LAG Stop Time
RO min 0 to 60 AV:202 MAIN_MS_lagstop
Lag Stop Timer
RO min 10 2 to 30 AV:332 CONF_MS_lstp_tim
Lead Lag Chiller Fault
0=No,1=Lead,2=Lag,3=Both
RO 0 0 to 3 AV:199 MAIN_MS_ll_fault
Lead Lag Communication
RO 0 0 to 1 BV:74 MAIN_MS_ll_comm
Lead Pulldown Time
RO min 0 0 to 60 AV:333 CONF_MS_lead_pul
Lead/Lag Balance Delta
RO hr 168 40 to 400 AV:330 CONF_MS_ll_bal_d
Lead/Lag Changeover?
RO BV:77 MAIN_MS_ll_chang
Lead/Lag Hours Delta
RO hour 0 –99999 to 99999 AV:206 MAIN_MS_ll_hr_d
Leaving Chilled Water
RO °F 0.0 –40.0 to 245 AV:26 TEMP_LCW
Leaving Condenser Water
RO °F 0.0 –40.0 to 245 AV:28 TEMP_LCDW
Line Current Phase 1
RO amp 0.0 AV:125 POWER_LN_AMPS1
Line Current Phase 1
RO amp 0.0 AV:146 MAIISMH_AMPS_H1
Line Current Phase 2
RO amp 0.0 AV:126 POWER_LN_AMPS2
Line Current Phase 2
RO amp 0.0 AV:147 MAIISMH_AMPS_H2
Line Current Phase 3
RO amp 0.0 AV:127 POWER_LN_AMPS3
Line Current Phase 3
RO amp 0.0 AV:148 MAIISMH_AMPS_H3
AV — Analog Value
BV — Binary Value
RO — Read Only
RW — Read Write