System information

104
APPENDIX D — BACnet OPTION (cont)
Table C — BACnet Point Table (cont)
LEGEND *Object names are built from CCN table name and CCN point name
combined for easy recognition.
POINT DESCRIPTION
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT
ID
BACNET OBJECT NAME*
Gas Torque Factor
RO °F 1 0.25 to 3.0 AV:314 CONF_OPT_gt_fact
Ground Fault CT Ratio:1
RO 150 150 AV:185 ISM_MCFG_gfct_rat
Ground Fault Current
RO amp 15 1 to 25 AV:182 ISM_MCFG_gf_amps
Ground Fault Persistence
RO cycles 5 1 to 10 AV:183 ISM_MCFG_gfp_pers
Ground Fault Phase 1
RO amp 0.0 AV:130 POWER_GRFT_1
Ground Fault Phase 1
RO amp 0.0 AV:152 MAIISMH_GRFT_H3
Ground Fault Phase 2
RO amp 0.0 AV:131 POWER_GRFT_2
Ground Fault Phase 2
RO amp 0.0 AV:151 MAIISMH_GRFT_H2
Ground Fault Phase 3
RO amp 0.0 AV:132 POWER_GRFT_3
Ground Fault Phase 3
RO amp 0.0 AV:150 MAIISMH_GRFT_H1
Ground Fault Protection
RO ENABLE DSABLE/ENABLE BV:69 ISM_MCFG_gfp_en
Ground Fault Start Delay
RO cycles 10 1 to 20 AV:184 ISM_MCFG_gfs_del
Guide Vane 1 Actual mA
RO mA 0.00 AV:75 INPUTS_GV1_MA
Guide Vane 1 Actual Ohms
RO ohms 0.0 AV:65 INPUTS_GV1_OHMS
Guide Vane 1 Decrease
RO OFF OFF/ON BV:32 OUTPUTS_GV1_DEC
Guide Vane 1 Increase
RO OFF OFF/ON BV:33 OUTPUTS_GV1_INC
Guide Vane/SRD Factor
RO 0.95 0.7 to 1.20 AV:315 CONF_OPT_gv_srd_f
Guide Vane1 Output mA
RO mA 0.00 0.00 to 20.8 AV:82 OUTPUTS_GV1_OUT
Guide Vane1 Type
0=Dig Po 1=Ana 2=Dig Ne
RO 0 0 to 2 AV:222 FACTORY_gv1_type
GV1 Close Surge Prote
RO % 3.0 2.0 to 4.0 AV:263 CFGSURGE_gvstp_sg
GV1 Closure at Startup
RO % 4.0 0.0 to 40.0 AV:305 CONF_OPT_gv1stpos
GV1 Pos Load @25%
RO % 6.4 0.0 to 83.0 AV:293 CONF_SRD_gv11_25
GV1 Pos Load @50%
RO % 22.9 0.0 to 83.0 AV:294 CONF_SRD_gv11_50
GV1 Pos Load @75%
RO % 41.3 0.0 to 83.0 AV:295 CONF_SRD_gv11_75
GV1 Position @Shutdown
RO % 0.0 0 to 100 AV:192 MAISWRST_gv1_shut
GV1 Travel Limit
RO % 80.0 30 to 100 AV:240 SERVICE1_gv1_lim
Head Pres Delta P 0%
RO psig 25.0 20.0 to 85.0 AV:311 CONF_OPT_hdp_0
Head Pres Delta P 100%
RO psig 50.0 20.0 to 85.0 AV:312 CONF_OPT_hdp_100
Head Pres Output mA
RO % 0.0 0.0 to 100.0 AV:78 OUTPUTS_HDPV_OUT
Head Pres Valve Option
RO DISABLE DISABLE/ENABLE BV:97 CONF_OPT_hdpv_opt
Head Pres Valve Tgt Pos
RO % 0.0 0.0 to 100.0 AV:81 OUTPUTS_hdpv_tgt
Head Pressure Min Output
RO % 0.0 0.0 to 100.0 AV:313 CONF_OPT_hdpv_min
Head Pressure Reference
RO ^psig 0.0 –6.7 to 420.0 AV:58 PRESSURE_HEAD_P
Heat Reclaim Option
RO NO YES/NO BV:86 FACTORY_heatrecl
Heating ECDW Setpoint
RW °F 104.0 63.0 to 150.0 AV:343 SETPOINT_ecdw_sp
Heating LCDW Setpoint
RW °F 113.0 68.0 to 150.0 AV:346 SETPOINT_lcdw_sp
HGBP Change Flag
Close=0,Hold=1,Open=2
RO 0 0 to 2 AV:122 MAISURGE_hgbp_chg
HGBP Close IGV1 Position
RO % 10.0 1.5 to 20 AV:307 CONF_OPT_hgcl_gv1
HGBP Low Load DB
RO ^F 1.0 0.5 to 2.0 AV:310 CONF_OPT_hgbp_ldb
HGBP Off DT for Low Load
RO ^F 4.0 0.5 to 10.0 AV:308 CONF_OPT_hgb_toff
HGBP On DT for Low Load
RO ^F 2.0 0.5 to 10.0 AV:309 CONF_OPT_hgb_ton
HGBP Open IGV1 Position
RO % 5.0 0.5 to 10.0 AV:306 CONF_OPT_hpop_gv1
HGBP Selection
Disable=0, Surge=1
Low Load=2,Comb=3
RO 0 0 to 3 AV:304 CONF_OPT_hgbp_sel
HGBP Valve Fully Closed
RO NO NO/YES BV:14 INPUTS_HGBP_FC
HGBP Valve Fully Opened
RO NO NO/YES BV:15 INPUTS_HGBP_FO
HGBP Valve Is Configured
RO DSABLE DSABLE/ENABLE BV:93 CONF_OPT_hgbp_opt
AV Analog Value
BV Binary Value
RO Read Only
RW Read Write