APPENDIX D — BACnet OPTION (cont)
Table C — BACnet Point Table (cont)
LEGEND *Object names are built from CCN table name and CCN point name
combined for easy recognition.
POINT DESCRIPTION
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT
ID
BACNET OBJECT NAME*
Delete ISM Config
RO NO NO/YES BV:66 ISM_MCFG_del_ismc
Demand Limit At 20 mA
RO % 40.0 10 to 100 AV:239 SERVICE1_dem_20ma
Demand Limit Prop Band
RO % 10.0 3.0 to 15.0 AV:238 SERVICE1_dem_pdb
Demand Limit Source
Amps=0,KW=1
RO 0 0 to 1 AV:5 GENCONF_DEM_SLCT
Demand Limit Source
Amps=0,KW=1
RO 0 to 1 BV:82 MAIN_MS_DEM_SLCT
Demand Limit Type
0 = Base Demand,1=4-20ma
RO 0 0 to 1 AV:3 GENCONF_dem_sel
Demand Watts Interval
RO min 15 5 to 60 AV:233 SERVICE1_dw_int
Derivatived EWT Gain
RO 2.0 1.0 to 3.0 AV:234 SERVICE1_ewtdgain
Deter Start Stop Command
RO BV:1 GENUNIT_statstop
DGT Override Flag
RO NO NO/YES BV:57 OVERRIDE_dgtov_fl
Diffuser Actual Pos
RO % 0.0 AV:68 INPUTS_DIFF_ACT
Diffuser Fault
RO NO NO/YES BV:63 MAIN_SRD_diffault
Diffuser Full Span mA
RO mA 18.0 15.0 to 22.0 AV:292 CONF_SRD_diff_ma
Diffuser Option
RO DSABLE DSABLE/ENABLE BV:89 CONF_SRD_diff_opt
Diffuser Output mA
RO mA 2.0 4.0 to 20.0 AV:77 OUTPUTS_DIFF_OUT
Diffuser Pressure
RO ^psig –10.0 –6.7 to 420.0 AV:57 PRESSURE_DIFF_P
Diffuser Target Pos
RO % 0.0 AV:159 MAIN_SRD_diff_tgt
Discharge Superheat
RO ^F 0.0 –20.0 to 99.0 AV:35 TEMP_DSH
Economizer Pressure
RO psig –10.0 –6.7 to 420.0 AV:53 PRESSURE_ECON_P
Emergency Stop
RO — — — BV:4 GENUNIT_EMSTOP_rd
Emergency Stop
RW 0 0 to 1 BV:104 GENUNIT_EMSTOP_wr
Emergency Stop Contact
RO OPEN OPEN/CLOSE BV:18 INPUTS_E_STOP
Enable Excessive Starts
RO 0 0 to 1 BV:87 SERVICE1_ex_start
Entering Chilled Water
RO °F 0.0 –40.0 to 245 AV:25 TEMP_ECW
Entering Condenser Water
RO °F 0.0 –40.0 to 245 AV:27 TEMP_ECDW
Evap Approach Alert
RO °F 5 0.5 to 15 AV:271 CFGLIMIT_evap_al
Evap Design Approach
RO °F 3 0 to 10 AV:339 CONF_PRG_ep_dgap
Evap Enter Water Pres
RO psig 0.0 –6.7 to 420.0 AV:89 HYDRLIC_EVAP_EWP
Evap Entering Water Pres
RO ^psig 0.0 –6.7 to 420.0 AV:59 PRESSURE_EVAP_EWP
Evap Flow Delta P Cutout
RO psig 5 0.5 to 50 AV:273 CFGLIMIT_evap_cut
Evap Flow Input (mA)
RO mA 0.0 AV:72 INPUTS_EVAPFLIN
Evap Freeze Active
RO NO NO/YES BV:44 MODES_evapfrze
Evap Leaving Water Pres
RO ^psig 0.0 –6.7 to 420.0 AV:60 PRESSURE_EVAP_LWP
Evap Leaving Water Pres
RO psig 0.0 –6.7 to 420.0 AV:90 HYDRLIC_EVAP_LWP
Evap Override Delta T
RO °F 3 2 to 5 AV:279 CFGLIMIT_ert_ovdt
Evap Refrig Liquid Temp
RO °F 0.0 –40.0 to 245 AV:30 TEMP_EVAP_T
Evap Refrig Trippoint
RO °F 33 0 to 40 AV:280 CFGLIMIT_ert_trip
Evap Sat Refrig Temp
RO °F –40.0 –40.0 to 245 AV:29 TEMP_EVAP_SAT
Evap Sat Temp @Shutdown
RO °F 0.0 –40 to 280 AV:193 MAISWRST_est_shut
Evap water flow Status
0=Fail or Not Started
1=Success, 2=Verifying
RO 0 to 2 AV:95 HYDRLIC_chw_fl_s
Evaporator Approach
RO ^F 0.2 0.0 to 99.0 AV:31 TEMP_evap_app
Evaporator Pressure
RO psig –10 –6.7 to 420.0 AV:51 PRESSURE_EVAP_P
EWT Control Option
RO BV:81 MAIN_MS_EWT_OPT
EWT Control Option
RW DSABLE DSABLE/ENABLE BV:102 SETPOINT_EWT_OPT
Factory Password
RO 4444 0 to 65535 AV:216 FACTORY_fac_pass
Fire Security Interlock
RO OPEN OPEN/CLOSE BV:23 INPUTS_FS_LOCK
Free Cooling Option
RO NO YES/NO BV:84 FACTORY_freecool
Frequency=60 Hz?(No=50)
RO NO NO/YES AV:181 ISM_MCFG_linefreq
AV — Analog Value
BV — Binary Value
RO — Read Only
RW — Read Write