System information

102
APPENDIX D — BACnet OPTION (cont)
Table C — BACnet Point Table (cont)
LEGEND *Object names are built from CCN table name and CCN point name
combined for easy recognition.
POINT DESCRIPTION
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT
ID
BACNET OBJECT NAME*
Cond Press Override Flag
RO NO NO/YES BV:50 OVERRIDE_cpov_fl
Cond Press Override High
RO psig 250 200 to 260 AV:277 CFGLIMIT_cpov_hi
Cond Press Override Low
RO psig 140 90 to 150 AV:276 CFGLIMIT_cpov_lo
Cond Sat Refrig Temp
RO c –40.0 –40.0 to 245 AV:33 TEMP_COND_SAT
Cond water flow Status
0=Fail or Not Started
1=Success, 2=Verifying
RO 0 to 2 AV:94 HYDRLIC_cdw_fl_s
Cond Water Pulldown/Min
RO ^F 0.0 –20 to 20.0 AV:88 HYDRLIC_cdw_pull
Condenser Approach
RO ^F 0.2 0.0 to 99.0 AV:32 TEMP_cond_app
Condenser Freeze Point
RO °F 34 –20 to 35 AV:270 CFGLIMIT_cdfreeze
Condenser Pressure
RO ^psig –10.0 –6.7 to 420.0 AV:52 PRESSURE_COND_P
Condenser Type
Low Pres=0,High Pres=1
RO 0 0 to 1 AV:214 FACTORY_cond_typ
Condenser Water Delta P
RO psig 0.0 –6.7 to 420.0 AV:87 HYDRLIC_cdw_pd
Condenser Water Flow
RO YES NO/YES BV:40 HYDRLIC_CDW_FLOW
Condenser Water Pump
RO OFF OFF/ON BV:42 HYDRLIC_CDWP
Control Mode
Local=0,Network=1
Remote=2,Local Sched=3
RO 0 to 3 AV:15 GENUNIT_ctl_mode
Control Point
RO AV:18 GENUNIT_CTRL_PNT_rd
Control Point
RW °F 45.0 10 to 160.0 AV:349 GENUNIT_CTRL_PNT_wr
Control Point Reset
RO ^F 0.00 –30.00 to 30.00 AV:19 GENUNIT_reset
Controlled DT Full Reset
RO ^F 10.0 –30.00 to 30.00 AV:13 RESETCFG_ctldt_fu
Controlled DT No Reset
RO ^F 0.0 0.0 to 15.0 AV:14 RESETCFG_ctldt_no
Controlled Fluid DB
RO ^F 1.0 0.5 to 2.0 AV:235 SERVICE1_ctrl_db
Controlled Water DT
RO ^F 0.0 –40.0 to 245 AV:93 HYDRLIC_ctrlw_dt
Controlled Water Temp
RO °F 0.0 AV:110 CAPACTRL_ctrl_wt
Cooling ECW Setpoint
RW °F 104.0 63.0 to 150.0 AV:344 SETPOINT_ecw_sp
Cooling LCW Setpoint
RW °F 45.0 10.0 to 120.0 AV:347 SETPOINT_lcw_sp
Cooling/Heating Select
RO AV:17 GENUNIT_HC_SEL_rd
Cooling/Heating Select
RW 0 to 1 AV:351 GENUNIT_HC_SEL_wr
Country Code
RO 86 0 to 500 AV:212 FACTORY_coun_cod
Current Alarm 1
RO AV:105 ALARMRST_alarm_1c
Current Alarm 2
RO AV:106 ALARMRST_alarm_2c
Current Alarm 3
RO AV:107 ALARMRST_alarm_3c
Current Alarm 4
RO AV:108 ALARMRST_alarm_4c
Current Alarm 5
RO AV:109 ALARMRST_alarm_5c
Current Umbal Persist
RO sec 5 1 to 10 AV:179 ISM_MCFG_cu_per
Current Umbal Threshold
RO % 5 1 to 10 AV:175 ISM_MCFG_cu_th
Damper Valve Act Delay
RO min 5 0 to 20 AV:243 SERVICE1_dmp_dly
Damper Valve Close
RO ON OFF/ON BV:30 OUTPUTS_DMP_CL
Damper Valve Close DB
RO psig 5.0 2.0 to 10.0 AV:246 SERVICE1_dmp_cldb
Damper Valve Full Closed
RO NO NO/YES BV:12 INPUTS_DMP_FC
Damper Valve Full Opened
RO NO NO/YES BV:13 INPUTS_DMP_FO
Damper Valve Open
RO OFF OFF/ON BV:31 OUTPUTS_DMP_OP
Damper Valve Open DB
RO psig 13.0 10.0 to 20.0 AV:247 SERVICE1_dmp_opdb
Damper Valve Status
Cl=0,Inter=1,Op=2,Fail=3
RO 1 0 to 3 AV:63 INPUTS_DMP_ACT
Damper Valve Tgt Pos
0=CL,1=Hold,2=Open
RO 0 0 to 2 AV:83 OUTPUTS_dmp_tgt
Deg Reset Water DT Full
RO °F 85.0 –40.0 to 245.0 AV:12 RESETCFG_drwdt_fu
Degrees Reset at 20mA
RW AV:8 RESETCFG_der_20ma
AV Analog Value
BV Binary Value
RO Read Only
RW Read Write