System information

101
APPENDIX D — BACnet OPTION (cont)
Table C — BACnet Point Table (cont)
LEGEND *Object names are built from CCN table name and CCN point name
combined for easy recognition.
†0 = OFF
1 = CTLTEST
2 = PUMPDOWN
3 = LOCKOUT
4 = RECYCLE
5 = TRIPOUT
6 = TIMEOUT
7 = PRESTART
8 = STARTUP
9 = AUTORST
10 = RAMPING
11 = RUNNING
12 = OVERRIDE
13 = DEMAND
14 = SHUTDOWN
POINT DESCRIPTION
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT
ID
BACNET OBJECT NAME*
Chilled Water Flow
RO NO NO/YES BV:43 HYDRLIC_CHW_FLOW
Chilled Water Pump
RO OFF OFF/ON BV:41 HYDRLIC_CHWP
Chiller Connection Type
0=Parallel, 1=Series
RO
0 0 to 1 AV:323 CONF_MS_ms_type
Chiller Lockout
RO OPEN OPEN/CLOSE BV:20 INPUTS_REM_LOCK
Chiller Run Status
OFF=0,Ready=1,ON=2
RO
0 0 to 2 AV:24 GENUNIT_ch_stat
Chiller State Number
RO 300 0 to 500 AV:23 GENUNIT_ch_state
Chiller Status Output mA
RO mA 8.0 4.0 to 20.0 AV:79 OUTPUTS_CHST_OUT
Chiller Type
NGC=0,Legacy=1
RO
0 0 to 1 AV:209 FACTORY_chil_typ
Common Sensor Option
RO DSABLE DSABLE/ENABLE BV:91 CONF_OPT_commsens
Communication Timeout
RO sec 60 0 to 255 AV:168 ISM_MCFG_com_tout
Comp (Single=0,Dual=1)
RO 0 0 to 1 AV:213 FACTORY_comp_typ
Comp Bearing Temp Alert
RO °F 175 155 to 175 AV:282 CFGLIMIT_tb_alert
Comp Bearing Temp Trip
RO °F 185 175 to 185 AV:283 CFGLIMIT_tb_trip
Comp Discharge Alert
RO °F 200 125 to 200 AV:278 CFGLIMIT_dgt_alrt
Comp Discharge Temp
RO °F 0.0 –40.0 to 245 AV:34 TEMP_DGT
Comp Frequency 100%
RO Hz 50.0 45.0 to 62.0 AV231 CONF_VFD_comp_100
Comp Motor Temp Override
RO °F 200 150 to 200 AV:281 CFGLIMIT_mt_over
Comp Motor Wind 1 Temp
RO °F 0.0 –40.0 to 245 AV:42 TEMP_MTRW1
Comp Motor Wind 2 Temp
RO °F 0.0 –40.0 to 245 AV:43 TEMP_MTRW2
Comp Motor Wind 3 Temp
RO °F 0.0 –40.0 to 245 AV:44 TEMP_MTRW3
Comp Thrust Bearing Temp
RO °F 0.0 –40.0 to 245 AV:37 TEMP_MTRB
Comp Thrust Lvg Oil Temp
RO °F 0.0 –40.0 to 245 AV:36 TEMP_MTRB_OIL
Compressor is Running
RO 5 BV:49 CAPACTRL_comp_run
Compressor Ontime
RO hour 0.0 0 to 500000.0 AV:99 RUNTIME_COMP_HRS
Compressor Run Contact
RO OPEN OPEN/CLOSE BV:11 INPUTS_RUN_AUX
Compressor Start Contact
RO OPEN OPEN/CLOSE BV:10 INPUTS_STAR_AUX
Compressor Start Relay
RO OFF OFF/ON BV:28 OUTPUTS_COMP_SR
Compressor1 Run Status
RO 0 to 14† AV:16 GENUNIT_cm_stas1
Compressor1 Run Status
RO 0 to 14 AV:200 MAIN_MS_lagstat
Cond Approach Alert
RO °F 6 0.5 to 15 AV:272 CFGLIMIT_cond_al
Cond Entering Water Pres
RO ^psig 0.0 –6.7 to 420.0 AV:61 PRESSURE_COND_EWP
Cond Entering Water Pres
RO psig 0.0 –6.7 to 420.0 AV:85 HYDRLIC_COND_EWP
Cond Flow Delta P Cutout
RO psig 5 0.5 to 50 AV:274 CFGLIMIT_cond_cut
Cond Flow Input (mA)
RO mA 0.0 AV:73 INPUTS_CONDFLIN
Cond Freeze Active
RO NO NO/YES BV:45 MODES_condfrze
Cond Hi Flow Alarm
RO DSABLE DSABLE/ENABLE BV:88 CFGLIMIT_cond_alm
Cond Hi Flow DP Limit
RO psig 50 0.5 to 50 AV:275 CFGLIMIT_cond_val
Cond Leaving Water Pres
RO ^psig 0.0 –6.7 to 420.0 AV:62 PRESSURE_COND_LWP
Cond Leaving Water Pres
RO psig 0.0 –6.7 to 420.0 AV:86 HYDRLIC_COND_LWP
Cond Press Cutout High
RO psig 275 270 to 275 AV285 CFGLIMIT_cpcut_hi
Cond Press Cutout Low
RO psig 160 155 to 160 AV:284 CFGLIMIT_cpcut_lo
AV Analog Value
BV Binary Value
RO Read Only
RW Read Write