System information

100
APPENDIX D — BACnet OPTION (cont)
Table C — BACnet Point Table
LEGEND *Object names are built from CCN table name and CCN point name
combined for easy recognition.
POINT DESCRIPTION
READ/
WRITE
UNITS
DEFAULT
VALUE
RANGE
BACNET
OBJECT
ID
BACNET OBJECT NAME*
Active Delta Tsat RO °F 0.0 AV:114 MAISURGE_dts_act
Active Demand Limit RO AV:22 GENUNIT_DEM_LIM_rd
Active Demand Limit RW % 10.0 10.0 to 100.0 AV:350 GENUNIT_DEM_LIM_wr
Actual Guide Vane 1 Pos RO % 0.00 AV:66 INPUTS_GV1_ACT
Actual Line Current RO amp 0.0 AV:128 POWER_AMPS_A
Actual Line Voltage RO V 0.0 AV:136 POWER_VOLT_A
Actual Setpoint RO °F 45.0 10.0 to 150.0 AV:20 GENUNIT_setpoint
Actual VFD Speed RO % 0.00 AV:67 INPUTS_VFD_ACT
Alarm Relay RO ON OFF/ON BV:26 OUTPUTS_ALM
Alarm Reset RO 0 0 to 1 BV:46 ALARMRST_RST_ALM
Alarm State RO AV:104 ALARMRST_ALM_STAT
Alert Relay RO ON OFF/ON BV:27 OUTPUTS_ALE
Amps Change Surge Prot RO % 0.0 AV:116 MAISURGE_amps_dta
Amps or KW Ramp Per Min RO % 10.0 5 to 20 AV:241 SERVICE1_ldramprt
Atmospheric Pressure RO psi 14.5000 8.000 to 15.000 AV:267 CFGSURGE_atom_pre
Auto Demand Limit Input RO mA 0.0 AV:69 INPUTS_AUTO_DEM
Auto Restart Active RO NO NO/YES BV:71 MAISWRST_auto_rst
Auto Restart Option RO DSABLE DSABLE/ENABLE BV:90 CONF_OPT_astart
Auto Water Temp Reset RO mA 0.0 AV:70 INPUTS_AUTO_RES
BACnet Dongle RO NO NO/YES BV:25 INPUTS_bacdongl
BACnet Enable RO 1 0 to 1 BV:100 BACNET_bacena
Base Demand Limit RW % 100.0 10.0 to 100.0 AV:348 SETPOINT_dem_base
Bearing Degradation RO °F 200 100 to 230 AV:340 CONF_PRG_beart_th
Cal Surge Delta Tsmax RO 0.0 0.0 to 150.0 AV:123 MAISURGE_dts_maxc
Cal Surge Delta Tsmax RO ^F 70.0 0.0 to 150.0 AV:253 CFGSURGE_dts_max
Cal Surge Delta Tsmin RO 0.0 0.0 to 150.0 AV:124 MAISURGE_dts_minc
Cal Surge Delta Tsmin RO ^F 45.0 0.0 to 150.0 AV:254 CFGSURGE_dts_min
Calc Actual Lift RO ^F 0.0 0.0 to 200.0 AV:47 TEMP_LIFT_A
Calc Actual Lift RO ^F 0.0 AV:163 MAIN_SRD_lift_a
Calc High Lift SRD Pos RO % 0.0 AV:161 MAIN_SRD_srd_1
Calc Low Lift SRD Pos RO % 0.0 AV:162 MAIN_SRD_srd_2
Calc Ref Delta Tsat RO °F –0.8 AV:115 MAISURGE_dts_cal
Calculated SRD Position RO % 0.0 AV:160 MAIN_SRD_srd_a
Capacity Decrease RO 0 0 to 1 BV:78 MAIN_MS_CAP_DECL
Capacity Decrease Flag RO ^F 0 BV:48 CAPACTRL_cap_dec
Capacity Inhibit RO 0 0 to 1 BV:79 MAIN_MS_CAP_INHL
Capacity Inhibit Flag RO NO NO/YES BV:47 CAPACTRL_cap_inh
Chill Water Pulldown/Min RO ^F 0.0 –20 to 20.0 AV:92 HYDRLIC_chw_pull
Chilled Medium RO WATER WATER/BRINE AV:215 FACTORY_chmedium
Chilled Water Delta P RO psig 0.0 –6.7 to 420.0 AV:91 HYDRLIC_chw_pd
AV Analog Value
BV Binary Value
RO Read Only
RW Read Write