Operating instructions
50
SV01L
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
7
Segment #12
Digital Output State
0 Bit0 Relay bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must
be set to accept value the from the sequencer:
P140, P142=27
Bit1 TB14
7
Segment #12 TB30
Analog Output Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #13
77
Segment #13
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse direction
77
Segment #13
Accel/Decel Time
20.0 0.0 {sec} 3600.0
77
Segment #13
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
77
Segment #13
Digital Output State
0 Bit0 Relay bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must
be set to accept value the from the sequencer:
P140, P142=27
Bit1 TB14
77
Segment #13 TB30
Analog Output Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #14
77
Segment #14
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse direction
77
Segment #14
Accel/Decel Time
20.0 0.0 {sec} 3600.0
77
Segment #14
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
77
Segment #14
Digital Output State
0 Bit0 Relay bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must
be set to accept value the from the sequencer:
P140, P142=27
Bit1 TB14
P77
Segment #14 TB30
Analog Output Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
Segment #15
7
Segment #15
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse direction
7
Segment #15
Accel/Decel Time
20.0 0.0 {sec} 3600.0
7
Segment #15
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
7
Segment #15
Digital Output State
0 Bit0 Relay bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must
be set to accept value the from the sequencer:
P140, P142=27
Bit1 TB14
7
Segment #15 TB30
Analog Output Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10