Operating instructions

46
SV01L
Commissioning
4.5.9 Sequencer Parameters
The P700 Sequencer parameters are listed herein. Refer to section 4.5.7 for P56x Sequencer Diagnostic Parameters.
Code Possible Settings
IMPORTANT
No. Name Default Selection
0
Sequencer Mode 0 0 Disabled If P700 = 0 and no reference (P121, P101)
points to any of the sequence segments, then
P701-P799 will not be displayed on the local
keypad.
1 Enabled: transition on timer only
2 Enabled: transition on rising edge (P121,
122, 123 = 25 step sequence)
3 Enabled: transition on timer or rising edge
7
Sequencer: TB13A
Trigger Segment
1 1 - 16
TB13A = lowest priority
Asserting TB13A with selection #24 (Start
Sequence), starts the sequence operation from
the segment specified in this parameter.
7
Sequencer: TB13B
Trigger Segment
1 1 - 16
TB13B: higher priority than TB13A
Asserting TB13B with selection #24 (Start
Sequence), starts the sequence operation from
the segment specified in this parameter.
7
Sequencer: TB13C
Trigger Segment
1 1 - 16
TB13C: higher priority thanTB13B, A
Asserting TB13C with selection #24 (Start
Sequence), starts the sequence operation from
the segment specified in this parameter.
7
(2)
Sequencer: TB13D
Trigger Segment
1 1 - 16
TB13D: higher priority than TB13C, B, A
Asserting TB13D with selection #24 (Start
Sequence), starts the sequence operation from
the segment specified in this parameter.
7
Sequencer: Action
after Stop/Start
transition or Fault
Restart
0 0 Restart at beginning of sequence Pointed by TB13x
1 Restart at beginning of current seg
2 Start at beginning of prior segment
3 Start at beginning of next segment
P7
Sequencer: Number
of cycles
1 1 65535 1 = single scan; 65535 = continuous loop
7
Sequencer: Time
units/scaling
0 0 0.1 {sec} 6553.5 Setup units/scaling for all sequencer time related
parameters
1 1 {sec} 65535
2 1 {min} 65535
NOTE:
P708 rescales the following sequencer related parameters:
- Segment Times in current step: P712, P717, P722, P727, P732, P737, P742, P747,
P752, P757, P762, P767, P772, P777, P782, P787, P792
- Sequence diagnostic/status: P561, P562
Segment #1
7
Segment #1
Frequency Setpoint
0.0 -500.0 {Hz} 500.0 If P112 = 1, negative sign forces reverse direction
P7
Segment #1
Accel/Decel Time
20.0 0.0 {sec} 3600.0
7
Segment #1
Time in current step
0.0
0
0.0 {P708} 6553.5
0 {P708} 65535
Scaling/units depend on P708
Skip segment if time = 0
7
Segment #1
Digital Output State
0 Bit0 Relay bit = 0: OFF (De-energized)
bit = 1: ON (Energized)
The corresponding digital output/relay must
be set to accept value the from the sequencer:
P140, P142=27
Bit1 TB14
7
Segment #1 TB30
Analog Output Value
0.00 0.00 {VDC} 10.00 TB30 configuration parameter must be set to
accept this value: P150 = 10
(2) Parameter applicable to SMV models 15HP (11kW) and higher.