Operating instructions
37
SV01L
Commissioning
Code Possible Settings
IMPORTANT
No. Name Default Selection
Motor Braking 0 Disabled
1 Braking with BUS threshold
2 Braking always on with deceleration
3 Braking with bus regulator
4 Special (Consult factory before using)
Motor Brake Level 0 0 {%} 75
(flux
braking
disabled)
Active when P190 > 0 and drive is in deceleration
mode. Use to reduce deceleration time on high
inertia loads.
NOTE: Over usage of P190 can cause frequent
‘overload’ trips “F.PF”
Not active for P300 = 5 (Torque mode)
9
Motor Braking
Deceleration
Reduction Level
0.0 0 P167
(base freq)
Raising the value of P191 reduces the
drive deceleration rate during flux braking.
Active when P190 > 0 and P192 > 0.0, Drive is
in deceleration mode. Use to reduce deceleration
time on high inertia loads.
NOTE: Usage of P192 can cause the drive to
decelerate faster than settings in P105/P127.
Not active for P300 = 5 (Torque mode)
P1
Password 0 0000 9999 • Must enter password to access parameters
• P194 = 0000: Disables password
Clear Fault History 0 0 No Action
1 Clear Fault History
Program Selection 0 Operate from User settings
1 Operate from OEM settings Refer to Notes 1, 2 and 3
2 Reset to OEM default settings Refer to Note 1
3 Reset to 60 Hz default settings • Refer to Note 4
• Parameters are reset to the defaults listed in
this manual.
• For P199=4, the following exceptions apply:
- P103, P152, P161, P167 = 50.0 Hz
- P304 = 50 Hz;
- P305 = 1450 RPM
- P107 = 0 (480 V drives only)
4 Reset to 50 Hz default settings
5 Translate Refer to Note 5
WARNING!
Modification of P199 can affect drive functionality! STOP and EXTERNAL FAULT circuitry may
be disabled! Check P100 and P121...P124
NOTE 1
If the EPM does not contain valid OEM settings, a flashing GF will be displayed when P199
is set to 1 or 2.
NOTE 2
When P199 is set to 1, the drive operates from the OEM settings stored in the EPM Module
and no other parameters can be changed ( will be displayed if attempted).
NOTE 3
Auto Calibration is not possible when operating from OEM Settings.
NOTE 4
Reset 60 and Reset 50 will set the Assertion Level (P120) to “2” (High). P120 may need to
be reset for the digital input devices being used. An fault may occur if P120 and the
Assertion switch are not set identically.
NOTE 5 - on next page.