4.5.3 Advanced Setup Parameters
Code Possible Settings
IMPORTANT
No. Name Default Selection
Analog Inputs
Configuration
0 TB5: (0-10 VDC); TB25: (4-20mA)
1 TB5: (0 - 5 VDC); TB25: (4-20mA)
2 TB5: (2 - 10 VDC); TB25: (4-20mA)
3 TB5: (-10 - +10 VDC); TB25: (4-20mA) Available on special option module only
4 TB5: (0-10 VDC); TB25: (0-20mA)
5 TB5: (0 - 5 VDC); TB25: (0-20mA)
6 TB5: (2 - 10 VDC); TB25: (0-20mA)
7 TB5: (-10 - +10 VDC); TB25: (0-20mA) Available on special option module only
7
TB5 (0-10V) Analog
Input Monitoring
Action
0 No Action Selects the reaction to a loss of the 0-10V signal
at TB5
Minimum time above/below Monitoring Level
(P158) before triggering action is 500ms.
1 P157 < P158 - Trip Fault F.FAU
2 P157 < P158 - Run Preset #8
3 P157 < P158 - Run Preset Seq. #16
4 P157 > P158 - Trip Fault F.FAU
5 P157 > P158 - Run Preset #8
6 P157 > P158 - Run Preset Seq. #16
TB5 (0-10V) Analog
Input Monitoring
Level (ML)
0.0 -10.0 {VDC} 10.0
0-10V Analog Input
Deadband
0.0 0 {VDC} 10.0 Not active if [-10 to +10 VDC] option is selected.
P
Speed at Minimum
Signal
0.0 -999.0 {Hz} 1000
f
P161
P160
ref
10V
(20mA)
0V
(4mA)
V0111
P1
Speed at Maximum
Signal
60.0 -999.0 {Hz} 1000
NOTE
• P160 sets the output frequency at 0% analog input
• P161 sets the output frequency at 100% analog input
• P160 or P161 < 0.0 Hz: For scaling purposes only; does not indicate opposite direction!
• P160 > P161: Drive will react inversely to analog input signal
p1
Analog Input Filter 0.01 0.00 {s} 10.00 Adjusts the filter on the analog inputs (TB-5 and
TB-25) to reduce the effect of signal noise
TB-25 (4-20mA)
Analog Input
Monitoring Action
0 0 No Action • Selects the reaction to a loss of the 4-20 mA
signal at TB-25.
• Signal is considered lost if it falls below 2 mA
• Digital outputs can also indicate a loss of 4-20
mA signal; see P140, P142
1 P163 < P164 - Trip Fault
2 P163 < P164 - Run Preset #7
3 P163 < P164 - Run Preset Seq. #15
4 P163 > P164 - Trip Fault
5 P163 > P164 - Run Preset #7
6 P163 > P164 - Run Preset Seq. #15