Instructions / Assembly
56
PROGRAMMING
T-SERIES
TRANSITION VPD SETTING
Adjusts how gradually your device will shift between 
levels when triggered ON by the VPD trigger. This 
will determine how much the probe VPD needs to 
increase to step up to the next level setting.
The higher the transition setting is, the wider the 
VPD gap is between levels. The lower the transition 
setting is, the smaller the VPD gap is between levels. 
If this figure is set to zero, your device will jump to 
your maximum level when triggered ON.
Press the up or down button to set a transition 
threshold between 0.1 kPa and 1.0 kPa. When the 
sensor VPD first reaches or crosses the VPD trigger 
point, the level will increase by one (exiting OFF 
Mode). Each time the threshold level is crossed, the 
level will ramp up by one until it reaches the level set 
in ON Mode.
EXAMPLE
In this example, your high VPD trigger is set at 0.1 
kPa, the OFF Mode level is 0, and the ON Mode 
level is 6. If the transition threshold is set to 0 kPa, 
then once the sensor temperature reaches or 
exceeds 0.1 kPa, the devices will trigger to run at 
level 6. However, if the transition threshold is set to 
0.2 kPa, then the devices will trigger to run at level 
1 when the VPD reaches or exceeds 0.1 kPa. It will 
then ramp up to level 2 when the VPD reaches or 
crosses 0.3 kPa, level 3 at 0.5 kPa, etc. From 1.1 
kPa on, it will run at level 6, the level set in ON Mode.