Special case: installation in a hallway with a width of < 3 m
< 3 m
• Maximum distance from
the front walls: 7.5 m
• Maximum distance between
detectors: 15 m
• Installation on the mitre line between
intersecting crossings, T-junctions and
corner areas
< 7,5 m
< 3 m
< 15 m
Special case: installation in an L-shaped room
RM
RM
RM
• Total area of < 60 m²: installation
on the mitre line
• Total area of > 60 m²: each side
is treated as a separate room