Specifications

Device Specification Data
IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 79
The following table is a summary of the most important models 267 / 269 FF specification
data.
Manufacturer ABB
Device Model 2600T Series Pressure Transmitter - Models 267 / 269
FOUNDATION Fieldbus
Device Type Link Master Device
Measured Variable Direct:
Differential, Absolute Pressure, Temperature
Derived:
Flow, Level and Volume (Flow only with 267Cx / 269Cx)
Output Signal Physical layer compliant to the standard IEC 1158-2
Communication speed 31.25 Kbit/second
Electrical Signal Manchester Code II
Power supply Bus Powered: 10.2 … 32 Volts limited to 17 / 24 Volts for IS
Interface FOUNDATION™ Fieldbus H1 Compliant with specification
V 1.5
Blocks implemented 3 Standard Analog Input, 1 Standard PID, 1 Enhanced
Resource, 1 Custom Pressure with Calibration Transducer
Blocks, 1 Temperature Transducer, 1 MV Block (only with
267Cx / 269Cx)
FB Execution period 80 ms for the AIFBs
100 ms for the PIDFB
100 ms for the MV (MV only with 267Cx / 269Cx)
LAS functionality 1 sub-schedule, 96 sequences, 25 elements for sequence
Number of link objects 25
Number of VCRs 24
Current consumption 12 mA
Fault Current limiting 19 mA
FF Registration IT023600
IS Certificate ATEX, FISCO
Max. Temperature -40 … 85 °C
Remote Configuration tools Via tools using DD & CFF Files, flow configuration with DMA