Specifications

Device Specification Data
78 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
13 Device Specification Data
The delivery of the models 265 / 267 / 269 FF includes the DD file (*.sym, *.ffo files) and the
Capability file (.CFF file).
The following table is a summary of the most important models 265 FF specification data.
Manufacturer ABB
Device Model 2600T Series Pressure Transmitter – Models 265
FOUNDATION Fieldbus
Device Type Link Master Device
Measured Variable Direct: Differential, Gauge, Absolute Pressure.
Derived: Flow, Level and Volume
Output Signal Physical layer compliant to the standard IEC 1158-2
Communication speed 31.25 Kbit/second
Electrical Signal Manchester Code II
Power supply Bus Powered: 10.2 … 32 Volts limited to 17 / 24 Volts for IS
Interface FOUNDATION™ Fieldbus H1 Compliant with specification
V 1.5
Blocks implemented 2 Standard Analog Input, 1 Standard PID, 1 Enhanced
Resource,
1 Custom Pressure with Calibration Transducer Blocks
FB Execution period 80 ms for the AIFBs
100 ms for the PIDFB
LAS functionality 1 sub-schedule, 96 sequences, 25 elements for sequence
Number of link objects 25
Number of VCRs 24
Current consumption 12 mA
Fault Current limiting 19 mA
FF Registration IT023700
IS Certificate ATEX, FISCO
Max. Temperature -40 … 85 °C
Remote Configuration tools Via tools using DD & CFF Files