Specifications
Process Flow
76 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Details for GOOD (cascade)
192 C0 1 1 0 0 0 0 = ok PID
196 C4 1 1 0 0 0 1 = initialisation
acknowledge
PID
200 C8 1 1 0 0 1 0 = initialisation
request
PID
204 CC 1 1 0 0 1 1 = non invited PID
224 E0 1 1 1 0 0 0 = initiate fault
state
PID
Initialisation Acknowledge detail:
The value is an initialised value from a source (cascade input, remote-cascade in, and remote-
output in parameters).
Initialisation Request detail:
The value is an initialised value for a source (back calculation input parameters), because the
lower loop is broken or the mode is wrong.
Not Invited detail:
The value is from a block, which does not have a target mode that would use this input. This
covers all cases other than Fault State Active, Local Override, and Not Selected. The target
mode can be the next permitted mode of higher priority in case of shedding a supervisory
computer.
Initiate Fault State detail:
The value is from a block that wants its downstream output blocks (e.g. AO) to go to Fault State.
This is determined by a block option to initiate Fault State is the status of the primary input
and / or cascade input goes Bad. See the status option table.