Specifications

Process Flow
IM/265/7/9/ADD/FF-EN_01 Connection to FOUNDATION Fieldbus 73
Configuration error detail:
Set if the AIFB Channel is different by 0 but set to a not valid / supported value. See the Table
on page 23 in this document for the supported Channel values.
Not Connected detail:
Set if this input is not referenced by a link object within the resource.
Device failure detail:
When malfunction in the device is detected this status is produced.
Sensor failure detail:
When malfunction of the sensor is detected, this status is produced.
No communication with last usable value (= LUV) detail:
Set if this value had been set by communication, which has now failed.
**Typically the Input variables of the PID are set to this status when the variable linked in input
and coming from another block fails.
No communication, with no usable value detail:
Set if there has never been any communication with this value since it was last Out of Service.
**Typically, the Input variables of the PID are set to this status when the variable linked in input
and coming from another block fails.
Out of Service detail:
This status is produced when the device is in Out Of Service mode.
When the TB_PRIMARY_VALUE_TYPE is selected for Flow and Volume measurement, some
specific parameters of the Transducer block have to be well configured by the customer. If the
configuration is not well done so the measure cannot be produced (i.e. negative value in input at
the Square Root operation), this status is set.
When the XD_SCALE is set different to the OUT_SCALE and the L_TYPE is not set to indirect,
this status is set.
2) Other variables like the Trimmed Value and the different SECONDARY_VALUE_x mapped in the TB, and several
variables of the PIDFB are produced with their own status byte.