Specifications

Process Flow
66 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
M00515
Block
Pressure
Transducer
2
MV
Temp.
VOL
Analog
1
Input
Temp.
Medium
OUT
Analog
OUT
Input
Pabs
Sensor
Temp.
Pabs
Temp.
DP
DP
Analog
3
OUT
Input
MASS
Block
Temp.
Transducer
Fig. 13: Connection between AIFB and TB with 267 / 269 Multivariable Transmitter for
Differential Pressure, Absolute Pressure, Temperature and Flow (MV Block, Mass-
and Volume-Flow only with 267Cx / 269Cx)
The connection between Analog Input Block and Transducer Block will be made with choosing
the same channel number for the CHANNEL parameter of the Analog Input Block and the
PTRB_CHANNEL_MAP parameter of the transducer block. Two output values (E. g.:
PRIMARY_VALUE and SECONDARY_VALUE) must always have different channel numbers.
The outputs for mass and volume flow are dedicated to the Multi Variable Function. These
outputs can also be given to an Analog Input with choosing the channel 1001 or 1002.