Specifications

Device Configuration
60 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Idx Name Byte PC Description
12 PRESSURE_DEFAULT 4 R Pressure replacement value. Replacement value of the
pressure. This value will be used by the flow calculation
algorithm instead of the measured value if this option is
selected (basically or at invalid input value).
1 R Temperature input. The temperature for flow calculation. 13 TEMPERATURE_IN
The temperature status for flow calculation.
14 TEMPERATURE_
UNIT
2 R Temperature unit.
Unit of all to the temperature belonging Values.
15 TEMPERATURE_
DEFAULT
4 R Temperature replacement value. Replacement value of the
temperature. This value will be used by the flow calculation
algorithm instead of the measured value if this option is
selected (basically or at invalid input value).
16 DEFAULT_INPUT_
SELECT
1 R Replacement values. Enables / Disables the basically use of a
replacement value instead of a measured value.
17 OUT_VOL_FLOW 1 R Volume flow output. Calculated volume flow in dependence of
differential pressure, pressure and temperature.
18 OUT_VOL_FLOW_
UNIT
2 R/W Volume flow unit. Unit of all to the volume flow belonging
Values (Output, Maximum value, Simulation values).
ATTENTION!
If the unit will be changed then the belonging values must be
adjusted.
19 OUT_MASS_FLOW 1 R Mass flow / Normalized volume flow output. Calculated mass
flow (Normalized volume flow at GAS) in dependence of
differential pressure, pressure and temperature.
20 OUT_MASS_FLOW_
UNIT
2 R/W Mass flow / Normalized volume flow unit. Unit of all to the mass
flow/normalized volume flow belonging Values (Output,
Maximum value, Simulation values).
ATTENTION!
If the unit will be changed then the belonging values must be
adjusted.
21 SIMULATE_DIFF_
PRESSURE
1 R/W SIMULATE dP
Allows the input value to the block to be manually supplied
when simulate is enabled. When simulate is disabled, the
simulate value and status track the actual value and status.