Specifications

Device Configuration
58 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Idx Name Byte PC Description
16 CAL_POINT_HI 4 R/W The Highest calibrated value.
17 CAL_POINT_LO 4 R/W The lowest calibrated value.
18 CAL_MIN_SPAN 4 R The minimum span to be used between the calibrations points,
high and low.
19 CAL_UNIT 2 R/W Calibration Unit. Only Temperature Units are allowed.
20 SENSOR_TYPE 2 R/W Type of sensor. Default is: 128 PT100 A 385.
4 R High Range
4 R Low Range
Sensor Temperature Unit. The allowed units are:
2 R Unit Index
21 SENSOR_RANGE
1 R Decimal
point
1000 Kelvin
1001 Celsius Degree
1002 Fahrenheit Degree
1003 Rankine Degree
22 SENSOR_SN 32 R Serial Number of the sensor.
23 SENSOR_CAL_
METHOD
1 R/W Calibration Method
24 SENS_CAL_LOC 32 R/W The last location of the sensor Calibration.
25 SENS_CAL_DATE 7 R/W The last date on which the calibration was performed.
26 SENS_CAL_WHO 32 R/W The name of the person responsible of the last sensor
calibration.
27 SENSOR_
CONNECTION
1 R/W The only possible value is: 4 Four Wire
28 SECONDARY_VALUE 1 R Only for internal use.
29 SECONDARY_
VALUE_UNIT
2 R/W Only for internal use.
30 MODULE_SN 4 R/W Sensor Serial Number
31 TTRB_
CHANNEL_MAP
2 R/W This parameter is for the correlation of channels in a device to
channels as defined for a plant or process area.
32 COMP_WIRE 4 R/W Only for internal use.
33 TTRB_BIAS 4 R/W Only for internal use.
34 TTRB_MAX_
SENSOR_VALUE
4 R/W Drag indicator for maximum temperature value. The drag
indicator will be reset by writing any value.
35 TTRB_MIN_
SENSOR_VALUE
4 R/W Drag indicator for minimum temperature value.
The drag indicator will be reset by writing any value.