Specifications

Device Configuration
52 Connection to FOUNDATION Fieldbus IM/265/7/9/ADD/FF-EN_01
Idx Name Byte PC Description
4 R/W This input is used as tack value when external tracking is
enabled by TRK_IN_D.
Expressed in TRK_SCALE Unit Code.
39 TRK_VAL
1 R/W Tracking Status
4 R/W The Feed-Forward Control Value. Expressed in FF_SCALE
Unit Code.
40 FF_VAL
1 R/W The Feed-Forward Control Status.
4 R/W High Range
4 R/W Low Range
2 R/W Unit Index
41 FF_SCALE
1 R/W Decimal point
All the values are associated with the
feed forward value (FF_VAL).
42 FF_GAIN 4 R/W The gain that the feed forward input is multiplied by before it is
added to the calculated control loop.
This alert is generated by any change to the static data.
1 R/W Unacknowledged
1 R Update State
8 R Time Stamp:
The date and time of when the alert was generated.
2 R Static Revision
43 UPDATE_EVT
2 R Relative Index
The block alarm is used for all configuration, hardware, and
connection failure or system problems in the block. The cause
of the alert is entered in the sub-code field. The first alert to
become active will set the Active Status in the status
parameter. As soon as the Unreported status is cleared by the
alert reporting task, another block alert may be reported
without clearing the Active Status, if the sub-code has
changed.
1 R/W Unacknowledged
1 R Alarm State
8 R Time Stamp:
The date and time of when the alert was generated.
2 R Subcode
44 BLOCK_ALM
1 R Value